Installation manual
69Uniflair LE Accessories Manual
Local Values: Fan speed modulation is controlled by the pressure reading taken by the sensor on
each unit.
Mean Values: Fan speed modulation is controlled by the average pressure reading taken by the
sensors on the units connected on a local network.
5. After setting the parameters, navigate to the main screen.
6. To save the data that has been entered, restart the unit.
7. Repeat steps 1–7 for each unit.
8. To exit, press the ESC key and navigate to the main screen.
N
OTE: Fan speed modulation settings can be determined through sensor reading of the unit, or by calculating
the average reading of all units on the LAN.
Configuring the LAN settings using the touchscreen
Path: Main > Configuration > Unit > Airflow > Group
1. Turn on the power to the unit and wait for the touchscreen to display.
NOTE: Settings may appear on a different screen.
2. Press Number of LAN Units.
3. Press Yes to enter your credentials.
4. Enter your credentials and begin configuration.
Number of LAN Units: Enter the number of units on the LAN
Number of Standby Units: Enter the number of units in standby
Sensor Values Used: Enter the number of sensor values used
Delta Temperature for Automatic Changeover: Enter the temperature
Delta Temperature to Switch to Local Control: Enter the temperature
Unit Rotation Time: Enter the required number of hours
Automatically Switchover to Standby Unit: Set as required
Rotate to Standby Unit Only on Alarm: Set as required
Exclude from Rotation: Set as required
Switchover Mode: Set as required
Switchover On Power Loss: Enable
Number of Days Between Rotation: Enter the number of required days between each rotation.
Hour of Rotation: Enter the hour for the rotation to take place.
Minute of Rotation: Enter the minute for the rotation to take place
LAN SETTINGS
Temp./Hum. Control
Mode: Local Values
Air Pressure Control
Mode: Local Values
LAN SETTINGS
Temp./Hum. Control
Mode: Local Values
Air Pressure Control
Mode: Mean Values