3. Insert the pCOWeb card into the pCO controller and ensure it is fully seated.
4. Secure the pCOWeb card to the pCO controller with the supplied cover.
5. Insert the Ethernet cable.
Configuration
Using the LED display
NOTE: If installing multiple units on the network, each unit needs a unique address to avoid conflicts.
1. Press the Prg on the display interface.
2. Select SETTINGS.
3. Enter the password.
4. Select SERIAL/MODEM SETTINGS.
5. Enter the following:
Serial Address: 001
Serial Speed: 19200
Protocol: Standard
6. To exit, press the ESC key and navigate to the main screen.
Using the touchscreen
Path: Main > Configuration > Unit > Communication
1. Turn on the power to the unit and wait for the touchscreen to display.
NOTE: Settings may appear on a different screen.
2. Enter your credentials and begin configuration.
BMS1 Serial Address: 001
BMS1 Serial Speed: 19200
BMS1 Serial Protocol: Standard
Remote ON/OFF Only Through Serial Communication: Enable
3. Press the Home button to return to the main screen.