Installation manual
Table Of Contents
- General Information
 - Commissioning
 - Operation
 - Network Management Card
 - CM Display
 - Maintenance
 - Troubleshooting
 

55Pumped Refrigerant System Operation and Maintenance
Troubleshooting
Problem 
Possible Cause Corrective Action
Display interface not 
operational, but 
equipment operates
• Display interface 
not connected 
properly
• Verify that the display interface cable is connected properly.
Alarms do not show up 
on monitoring equipment 
(Customer Output 
Contact)
• External 
monitoring 
equipment is not 
receiving power or 
is not functioning 
properly
• Confirm that power, if required, is being supplied to the external 
equipment.
• If the RDU is providing power to the external equipment, verify that the 
external equipment is <
50 mA.
• Test the external equipment by bypassing the customer output contact.
Equipment does not shut 
down on command
• Drive voltage • Verify that there is a drive voltage entering the input of the RDU. You 
may use the +12 V or +24 V. You must also use the ground.
No communication with 
building management 
system (BMS) port
• Improper 
connection
• Confirm that the RDU is connected to the BMS port and not to the 
Control port.
• Make sure that the wire polarity is correct. Using a DC voltmeter, test the 
signal with no transmissions in progress. Expect the voltage at pin 2 to 
be greater than at pin 1 by at least 200 mV. Measure the RDU with the 
cable disconnected, and then measure it again with the cable connected. 
If the signal is less than 200 mV, the RDU may be reverse-wired.
• Make sure every CM has either two sets of wires on the connector or one 
set of wires and a terminating resistor of 100 to 120 ohms.
Cooling modules are not 
communicating with the 
RDU
• A-Link failure • Verify that the first and last cooling modules have one cable and a 
terminator.
• Verify that every other cooling module has two cables.
• Confirm that the A-Link cables are connected to the A-Link ports and 
that a network cable is connected to the network port.
• Verify that the number of cooling modules in the cooling group matches 
the group number setting.
Equipment does not shut 
down on command
• Drive voltage • Verify that there is a drive voltage entering the input of the cooling unit. 
You may use the available +12 V or +24 V. You must also use the 
ground.
No communication with 
building management 
system (BMS) port
• Improper 
connection
• Confirm that the RDU is connected to the BMS port and not to the 
Control port.
• Make sure that the wire polarity is correct. Using a DC voltmeter, test the 
signal with no transmissions in progress. Expect the voltage at pin 2 to 
be greater than at pin 1 by at least 200 mV. Measure the RDU with the 
cable disconnected, and then measure it again with the cable connected. 
If the signal is less than 200 mV, the RDU may be reverse-wired.
• Make sure that every CM has either two sets of wires on the connector or 
one set of wires and a terminating resistor of 100 to 120 ohms.
CMs are not 
communicating with 
each other
• A-Link failure • Verify that the first and last CMs have one cable and a terminator.
• Verify that every other cooling module has two cables.
• Confirm that the A-Link cables are connected to the A-Link ports and 
that a network cable is connected to the network port.
• Verify that the number of CMs in the cooling group matches the group 
number setting.
Output air is 17° C 
(62° F) and CM fans are 
running at a very high 
rate of speed.
•Upper or lower 
supply air sensor
• Either the upper or lower supply air temperature sensor has a fault. 
Verify that both supply air temperature sensors are installed and working 
properly.










