Service access
An area of minimum 900 mm (36 in) of clear floor space in front of and behind the equipment is
recommended for servicing (208V equipment), or 1067 mm (42 in) for servicing 400V and 480V
equipment. All required normal maintenance can be performed from the front or rear of the equipment
while in the row.
An area of minimum 1200 mm (48 in) of clear floor space in front of or behind the equipment is
recommended to roll the equipment out of a row.
Note: Check local and national codes and regulations for further service access requirements
Dimensions are shown in mm (in).
na1825a
Maintenance access required
when located in the row
Access
required to roll
out of the row