User manual
InRow RC Installation32
Description of user interface connectors
Item Description
Rack temperature sensors 1, 2, 3 Three temperature sensors which must be
installed on the cold aisle side of the server
racks. See “Rack temperature sensors” on
page 33.
A-Link IN In and out connections for A-Link. The
terminators supplied with the equipment
must be plugged into the first A-link port and
the final A-Link port for the group.
A-Link OUT
Network port 10/100 Base-T Network port. Connects the
equipment to the network; Status and Link
LEDs indicate network traffic.
• Status LED—blinks orange and green at
start-up; indicates the status of the network
connection (solid green—IP address
established; blinking green—attempting to
obtain an IP address).
• Link LED—blinks to indicate network
traffic (green—operating at 10 mbps;
orange—operating at 100 mbps).
Console port RS-232 communication port used for local
service access to the equipment. Use
configuration cable (APC part number
940-0103) to connect to this port.
Customer output, Normally Closed
(NC)
Customer-configurable output relay which
can be activated for all types of alarms or
critical alarms. The relay can be connected to
external equipment using 30 VAC/DC, 2 A.
Customer output, Common (COM)
Customer output, Normally Open (NO)
Supply GND Can be used for customer input and output
interface.
Supply 12 Vdc Can be used for customer input and output
interface. Current limit is 20 mA.
Supply 24 Vdc Can be used for customer input and output
interface. Current limit is 20 mA.
Customer input + Used for remote shutdown of the InRow RC.
Voltage is applied from the internal power
supply or by using an external power supply.
Supply COM- Ground connection point for remote
shutdown supply source.
Modbus D1 (RXTX+) Connections for Building Management
System. Wire a 150-Ohm terminator resistor
(supplied) into the final InRow RC, between
Modbus D0 and Modbus D1.
Modbus D0 (RXTS–)
Modbus GND
Supply air temperature sensor (front) Temperature sensor installed on the front of
the equipment.
Supply air humidity sensor (front) Humidity sensor installed on the front of the
equipment.
Display interface Connection for the display interface installed
on the front door of the equipment.