User manual

InRow RC Installation38
Top routing
1. Remove the factory-installed knockout plate from the top of the
equipment.
2. Enlarge the two pilot holes in the knockout plate as needed to accept
conduit connectors.
3. Attach the conduit connectors to the knockout plate.
4. Secure the knockout plate to the top of the equipment.
5. Route power cabling to the main breakers as shown.
6. Connect feed A and B power wiring to the tops of the two main circuit breakers using the torque
specified on the breakers. Connect the phases of the two power feeds as marked next to the
terminals.
7. Connect the ground wires to the ground terminal block located above the main circuit breakers.
8. Reinstall the connection plate and the electrical panel cover.
Bottom routing
1. Locate the supplied knockout plate.
2. Install the knockout plate on the top of the equipment where you removed
the power connection plate and power cords.
3. Locate the power connection plate in the bottom of the unit. See “Bottom
piping and power access locations (bottom view)” on page 15.
4. Loosen the screw securing the connection plate, and remove the plate.
5. Enlarge the two pilot holes in the connection plate as needed to accept
conduit connectors.
6. Attach the conduit connectors to the connection plate. Secure the
connection plate to the bottom of the equipment.
7. Route the cabling to the main breakers as shown.
8. Fasten the cabling inside the unit with the provided tie wraps.
9. Connect feed A and feed B power wiring to the tops of the two main circuit
breakers using the torque specified on the breakers. Connect the phases of
the two power feeds as marked next to the terminals.
10.Connect the ground wires to the ground terminal block located just above
the main circuit breakers.
11. Reinstall the connection plate and the electrical panel cover.
na2309a
F
E
E
D
A
F
E
E
D
B