Specifications

InRow RP CW Installation26
Condensate pump
The pump is factory-wired and
piped internally to the condensate
drain pan and humidifier outlet.
The pump can move liquid a
maximum of 18 m (60 ft), which
may include a maximum lift of
3.5 m (11.5 ft) at a flow rate of 87
l/hr (23 gph). For example, if your
lift is 3 m (10 ft), you will have 15
m (50 ft) of usable run remaining.
The pump uses an on-board
condensate high level float switch
wired into the equipment for alarm
capabilities.
The condensate drain line can be connected through either the top or the bottom of the
equipment using factory-installed male quick connectors and tubing approved by local
building codes that will allow the drain line connector to be moved approximately 25
mm (1 in) away from the equipment. This facilitates removing the equipment from a
row. Female quick connectors and reduction fittings are supplied with the equipment.
Connect the fittings as shown, then connect the drain line quick connector to the top or
bottom condensate pump output line.
Note: Perform all piping in accordance with applicable industry guidelines as well as local
and national codes and regulations.
Warning: Failure to properly route the condensate pump drain line before operation
could result in water damage.
Warning: Do not route drain or supply lines above computer equipment,
Uninterruptible Power Supply (UPS) units, Power Distribution Units (PDUs), or light
fixtures.
Flexible tubing (field supplied and installed)
1/2-in male NPT or 1/2-in male BSPT fitting
(field supplied and installed)
Straight reduction (supplied)
Quick connector (supplied)
na2345b
Connection
through top
Connection
through bottom
na2534a