Specifications
InRow RP CW Installation40
Power Connections
Wiring configurations
Electrical Hazard: Only a licensed electrician may connect the equipment to utility power.
Route incoming power from the PDU to the electrical panel located in the left side of the equipment.
Power can be routed either through the top or the bottom.
Top routing
1. Roll the unit into the row.
2. Remove the electrical panel cover. See “Removing the electrical panel
cover” on page 21.
3. Locate the power connection plate in the top of the unit. See “Top piping
and power access locations (top view)” on page 16.
4. Loosen the screw securing the connection plate, and remove the plate.
5. Attach the conduit connectors using the pilot hole in the connection plate.
6. Route the cabling to the main breakers as shown.
7. Connect feed A and B power wiring to the tops of the two main circuit breakers using the torque
specified on the breakers. Connect the phases of the two power feeds as marked next to the
terminals.
8. Connect the ground wires to the ground terminal block located above the main circuit breakers.
9. Reinstall the connection plate and the electrical panel cover.
Bottom routing
1. Roll the equipment into the row.
2. Remove the electrical panel cover. See “Removing the electrical panel
cover” on page 21.
3. Locate the power connection plate in the bottom of the unit. See “Bottom
piping and power access locations (bottom view)” on page 17.
4. Loosen the screw securing the connection plate, and remove the plate.
5. Attach the conduit connectors using the two pilot holes in the connection
plate.
6. Route the cabling to the main breakers as shown.
7. Fasten the cabling inside the unit with the provided wire ties.
8. Connect feed A and feed B power wiring to the tops of the two main circuit
breakers using the torque specified on the breakers. Connect the phases of
the two power feeds as marked next to the terminals.
9. Connect the ground wires to the ground terminal block located just above
the main circuit breakers.
10.Reinstall the connection plate and the electrical panel cover.
na2328a