Specifications

41InRow RP CW Installation
Strain relief (ACRP502 only)
Adjustable metal strain reliefs are provided. See “Install kit inventory” on page 5.
1. Hook one strain relief into a pair of slots in each
of the two locations shown.
2. Route the electrical cable up from the bottom of
the equipment, passing through the strain reliefs.
3. Tighten the screws on the strain reliefs to capture
the electrical cable, taking the weight off of the
inner conductors.
4. Continue connecting electrical wiring to the
circuit breaker.
Voltage selection
Your equipment can operate at various supply voltages, provided the proper
voltage jumpers are connected to the input transformers. Read the part
number on the jumpers connected at the factory and compare that number to
the table below. If the correct jumpers for your input voltage are not
connected, remove them and connect the proper jumper.
Jumper Connections
Transformer B connected to J51 ()
Transformer A connected to J50 ()
SKU Input Voltage
Use Jumper
Part Number
ACRP500
208 (50/60 Hz) 0W2540 (default)
230 (50/60 Hz) 0W2541
ACRP501
460 (60 Hz) 0W2545
480 (60 Hz) 0W2546 (default)
ACRP502
380 (50/60 Hz) 0W2542
400 (50/60 Hz) 0W2543 (default)
415 (50/60 Hz) 0W2544
na2542a
na2540a