Rack ATS AP44xx User Manual12
Load Status LED
This LED identifies overload and warning conditions for the ATS. For more information on warning
conditions, see “Configure warning thresholds” on page 85.
Network Status LED
This LED indicates the network status.
10/100 Status LED
This LED indicates the network status of the Rack ATS.
Condition Description
Green The Rack ATS current is below the Near Overload Warning threshold.
Yellow The Rack ATS current is above the Near Overload Warning threshold.
Red The Rack ATS current is above the Overload Alarm threshold.
Condition Description
Off One or more of the following situations exists:
• The Rack ATS is not receiving input power.
• The cable that connects the Rack ATS to the network is disconnected
or defective.
• The device that connects the Rack ATS to the network is off or not
operating correctly.
• The Rack ATS is connected to an unknown network.
• The Rack ATS is not operating properly. It may need to be repaired or
replaced. Contact customer support at
www.apc.com/support.
Flashing green The Rack ATS is receiving data packets from the network at 10 Megabits
per second (Mbps).
Flashing orange The Rack ATS is receiving data packets from the network at 100
Megabits per second (Mbps).
Solid green or orange The Rack ATS is receiving no network traffic.
Condition Description
Off One or more of the following situations exists:
• The Rack ATS is not receiving input power.
• The cable that connects the Rack ATS to the network is disconnected or
defective.
• The device that connects the Rack ATS to the network is disconnected or
defective.
• The device that connects the Rack ATS to the network is turned off.
• The Rack ATS is connected to an unknown network.
• The Rack ATS is not operating properly. It may need to be repaired or
replaced. Contact customer support at
www.apc.com/support.
Solid green The Rack ATS has valid TCP/IP settings.
Flashing green The Rack ATS does not have valid TCP/IP settings.*
Solid orange A hardware failure has been detected in the Rack ATS.
Flashing orange The Rack ATS is making BOOTP requests.
Flashing orange and green
(alternating)
The Rack ATS is making DHCP requests.
*If you do not use a BOOTP or DHCP server, see “TCP/IP Configuration Methods” on page 6 for more
options.