User Manual
61Rack ATS AP44xx User Manual
bkNearOver
Access: Super User, Administrator, Device User
Description: Set or view the bank near-overload threshold current in amps. Only single phase SKUs
with two or more circuit breakers support this command.
Parameters:
Example:
apc> bkNearOver all 10
E000: Success
apc> bkNearOver all
E000: Success
1: 10 A
2: 10 A
total: 16 A
apc> bkNearOver 1
E000: Success
1: 10 A
apc> bkNearOver 1 12
E000: Success
apc> bkNearOver 1–2 10
E000: Success
Error Messages: E000, E102:
Argument Description
<all | bank#> • all: all bank numbers
•
bank#: A single number, a range of numbers separated with a dash, or a
comma-separated list of single bank number and/or number ranges.
<current> The new bank threshold (Amps)
NOTE: The maximum bank number is 3. If the ATS has only two circuit breakers, a total bank threshold is
provided.