User Manual
Rack ATS AP44xx User Manual62
bkOverLoad
Access: Super User, Administrator, Device User
Description: Set or view the bank overload threshold current in amps. Only single phase SKUs with two
or more circuit breakers support this command.
Parameters:
Example:
apc> bkOverLoad all
E000: Success
1: 14 A
2: 14 A
total: 24 A
apc> bkOverLoad 1
E000: Success
1: 14 A
apc> bkOverLoad 1 16
E000: Success
apc> bkOverLoad 1–2 16
E000: Success
Error Messages: E000, E102
Argument Description
<all | bank#> • all: all bank numbers
•
bank#: A single number, a range of numbers separated with a dash, or a
comma-separated list of single bank number and/or number ranges.
<current> The new bank threshold (Amps)
NOTE: The maximum bank number is 3. If the ATS has only two circuit breakers, a total bank threshold is
provided.