User Manual
Rack ATS AP44xx User Manual64
bkReading
Access: Super User, Administrator, Device User, Read Only
Description: View the current reading (measurement) in amps for a bank. Only single phase SKUs with
two or more circuit breakers support this command.
Parameters:
Example:
apc> bkReading 1
E000: Success
1: 6.3 A
apc> bkReading all
E000: Success
1: 6.3 A
2: 5.1 A
total: 11.4 A
apc> bkReading 1-2
E000: Success
1: 6.3 A
2: 5.1 A
Error Messages: E000, E102
Argument Description
<all | bank#> • all: all bank numbers
•
bank#: A single number, a range of numbers separated with a dash, or a
comma-separated list of single bank number and/or number ranges.
NOTE: The maximum bank number is 3. If the ATS has only two circuit breakers, a total bank threshold is
provided.