eventCounts
Access: Super User, Administrator, Device User
Description: Display or clear the event counts reported from the ATS controller.
Parameters:
Enter a <0> argument to set all event counts to 0.
Example:
apc> eventCounts
E000: Success
Event Counts
------------
Redundancy Loss: 15
Source Switch: 80
Over Current: 0
Source Preference Change: 7
Spike/Dropout: 95
Surge/Droop: 0
Frequency out of Range: 9
Error Messages: E000, E100, E102
freqDeviat
Access: Super User, Administrator, Device User
Description: Read or set the range of acceptable frequency fluctuation (Hz).
Parameters:
Example:
apc> freqDeviat
E000: Success
Frequency Deviation: 3 Hz
Error Messages: E000, E100, E102
Argument Description
<3 | 5 | 10> The new range of acceptable frequency deviation: 3, 5, or 10 Hz above or
below the nominal frequency.
If the Frequency (see “atsMeasure” on page 59) is at 50 Hz and vSensitvty (page 71) is set to High, freqDeviat
should be 3 or 5.