User Manual
67Rack ATS AP44xx User Manual
lineVRMS
Access: Super User, Administrator
Description: Read or set the nominal source line voltage (V).
Acceptable values depend on the SKU# of
your ATS.
Parameters: [<voltage>]
Example:
apc> lineVRMS
E000: Success
Nominal Line Voltage: 120
apc> lineVRMS 124
E000: Success
Error Messages: E000, E100, E102
phLowLoad
NOTE: Only units without circuit breakers are supported by this command.
Access: Super User, Administrator, Device User
Description: Set or view the phase low-load threshold in amps.
Parameters: <current>
Example:
apc> phLowLoad
E000: Success
0 A
apc> phLowLoad 3
E000: Success
Error Message: E000, E102
SKU Acceptable values
AP4421, AP4422, AP4423, AP4424 230
AP4430, AP4430X914, AP4432 200 or 208
AP4431, AP4433, AP4434 208
AP4450 100 or 120
AP4452, AP4452X631, AP4453 120
AP4452J 100