User Manual

Rack ATS AP44xx User Manual70
sourceBName
Access: Super User, Administrator, Device User
Description: Set or view the name of power source B.
Parameters: <sourceBName>
Example:
apc> sourceBName
E000: Success
Wall Box Phase L2
apc> sourceBName “Wall Box N2 Phase L3”
E000: Success
Error Messages: E000, E102
sourcePref
Access: Super User, Administrator, Device User
Description: Set or view the desired source preference.
Parameters: <A | B | None>
Example:
apc> sourcePref
E000: Success
Preferred Source: Source A
apc> sourcePref B
E000: Success
Error Messages: E000, E102
vMediumLmt
Access: Super User, Administrator, Device User
Description: Set or view the voltage range to use when the Voltage Transfer Range is set to Medium.
This value must be greater than the Narrow Transfer Limit and less than the Wide Limit (V).
Parameters: [<limit>]
The value range depends on the SKU:
Example:
apc> vMediumLmt
E000: Success
Voltage Medium Limit: 12 V
apc> vMediumLmt 14
E000: Success
Error Messages: E000, E100, E102
SKU Acceptable values
AP4421, AP4422, AP4423, AP4424 16–25
AP4430, AP4430X914, AP4432, AP4433, AP4434 15–30
AP4452J 10–15
AP4450, AP4452, AP4452X631, AP4453 10–23