User Manual

71Rack ATS AP44xx User Manual
vNarrowLmt
Access: Super User, Administrator, Device User
Description: Set or view the voltage range to use when the Voltage Transfer Range is set to Narrow.
This value must be less than the Medium Limit.
Parameters: [<limit>]
The value range depends on the SKU:
Example:
apc> vNarrowLmt
E000: Success
Voltage Narrow Limit: 15 V
Error Messages: E000, E100, E102
vSensitvty
Access: Super User, Administrator, Device User
Description: Set or view the sensitivity.
Parameters:
Example:
apc> vSensitvty
E000: Success
Voltage Sensitivity: Low
apc> vSensitvty High
E000: Success
Error Messages: E000, E100, E102
SKU Acceptable values
AP4421, AP4422, AP4423, AP4424 16–25
AP4430, AP4430X914, AP4432, AP4433, AP4434 15–30
AP4452J 10–15
AP4450, AP4452, AP4452X631, AP4453 10–23
Argument Description
<High | Low> Set the sensitivity of the ATS.
High: The ATS will switch power sources after 2ms when there is a
disturbance in the power supply.
Low: The ATS will switch sources after 4ms when there is a disturbance in
the power supply
NOTE: If the Frequency is at 50 Hz (see “atsMeasure” on page 59) and FreqDeviat is set to 10, vSensitvty
should be set to
Low.