User Manual
Rack ATS AP44xx User Manual72
vWideLmt
Access: Super User, Administrator, Device User
Description: Set or view the voltage range to use when Voltage Transfer Range is set to Wide. This
value must be greater than the Medium Limit.
Parameters:
[<limit>]
The configurable limit depends on the SKU:
Example:
apc> vWideLmt
E000: Success
Voltage Wide Limit: 20
apc> vWideLmt 24
E000: Success
Error Messages: E000, E102
vXferRange
Access: Super User, Administrator, Device User
Description: Set or view the Voltage Transfer Range. If the voltage of an ATS exceeds the Transfer
Range, it generates an alarm.
Parameters:
Example:
apc> vXferRange
E000: Success
Voltage Transfer Range: Medium
apc> vXferRange Wide
E000: Success
Error Messages: E000, E102
SKU Acceptable values
AP4421, AP4422, AP4423, AP4424 16–25
AP4430, AP4430X914, AP4432, AP4433, AP4434 15–30
AP4452J 10–15
AP4450, AP4452, AP4452X631, AP4453 10–23
Argument Description
<Wide | Medium |
Narrow>
Set the Voltage transfer range.
•
Wide: corresponds to configured values for vWideLmt.
•
Medium: corresponds to configured values for vMediumLmt.
•
Narrow: corresponds to configured values for vNarrowLmt.