Configure warning thresholds
Path: Configuration > ATS > Load
Status: View the current in A, and the Peak Current in kVA, for the device, phases, and banks. The
indicator in the green, yellow, and red meter shows the load status: normal, near overload, or overload.
Warning Thresholds: The Rack ATS generates an alarm when any bank exceeds its rated value. Set
the number of amps to trigger a Low Load Warning, Near Overload Warning, and Overload Alarm.
NOTE: If a circuit breaker trips, there is no definitive indication that the circuit breaker is open. However,
the current for that bank will drop. Set the Low Load Warning to 1 amp for these reasons :
• The default setting for the Low Load Warning is 0 amps. This effectively disables the warning; with
this setting, the Web UI will not indicate that a circuit breaker may have been tripped.
• A 1-amp detection threshold for the Low Load Warning will help to indicate that a circuit breaker
may have tripped.
Peak Current: Reset the peak current.
Click Apply to save your changes or Cancel to erase your changes.