User Manual

Customer support and warranty information is available
at www.apc.com.
© 2015 Schneider Electric. All trademarks are owned by
Schneider Electric Industries S.A.S.
990-3561A
10/2015
Specifications
en
Electrical
Input connection NEMA L6-30P cord included
Acceptable input voltage 200–240 VAC +6% to -10%
Maximum input current
(phase)
30 A (24 A UL/C-UL derated)
Input frequency 50/60 Hz
Output voltage 200–240 VAC +6% to -10%
Output connections (4) C19
Maximum output
current (outlet)
C19; 16 A (UL/C-UL derated)
C19; 20 A (PSE)
Maximum output
current (phase)
30 A (24 A UL/C-UL derated)
Maximum output
current (bank)
16 A UL/C-UL derated)
20 A (PSE)
Overcurrent protection
(internal)
(2) 20 A, 2-pole breakers
Cord length 3.65 m (12.00 ft)
Physical
Dimensions
(H x W x D)
43.81 x 4.36 x 12.57 cm
(17.25 x 1.72 x 4.95 in)
Shipping dimensions
(H x W x D)
47.29 x 28.09 x 18.00 cm
(18.62 x 11.06 x 7.09 in)
Weight 3.80 kg (8.36 lb)
Shipping weight 4.60 kg (10.12 lb)
Environmental
Maximum elevation
(above MSL)
Operating
Storage
0 to 3048 m (0 to 10,000 ft)
0 to 15 240 m (0 to 50,000 ft)
Temperature
Operating
Storage
0 to 50°C (32 to 122°F)
–15 to 60°C (5 to 140°F)
Humidity
Operating
Storage
5 to 95%, non-condensing
5 to 95%, non-condensing
Compliance
Safety approvals UL/C-UL
ROHS 2011/65/EU – latest revision