Technical information
Chapter 3:
How to Use OIDs for 3-Phase UPS Models
PowerNet MIB Reference Guide
25
How to Use OIDs for 3-Phase UPS Models
The [upsPhase] category has OIDs in three subcategories
• [upsPhaseResetValues]: Set of OIDs you use to reset the counters for the corresponding OID
in the [upsPhaseInput] and [upsPhaseOutput] groups that report minimum and maximum
values.
• [upsPhaseInput]: Set of OIDs you use to obtain information about the input phases.
• [upsPhaseOutput]: Set of OIDs you use to obtain information about the ouput phases.
To access the values of OIDs in a table, select the OID table in the SNMP browser. (An OID table
appears enclosed in braces {}.) For example, to access the OIDs that provide information on all input
phases for a device, select {upsPhaseInputPhaseTable} in the SNMP browser, and then select
[upsPhaseInputEntry] to see each OID in the table.
[upsPhaseResetValues]
Use an OID in the [upsPhaseReset Values] group to reset the counters for the corresponding OID in
the [upsPhaseInput] and [upsPhaseOutput] groups that report minimum and maximum values.
OID Task
upsBasicControlConserveBattery
upsPhaseInputMaxVoltage
upsPhaseInputMinVoltage
upsPhaseInputMaxCurrent
upsPhaseInputMinCurrent
upsPhaseInputMaxPower
upsPhaseInputMinPower
upsPhaseOutputMaxCurrent
upsPhaseOutputMinCurrent
upsPhaseOutputMaxLoad
upsPhaseOutputMinLoad
upsPhaseOutputMaxPercentLoad
upsPhaseOutputMinPercentLoad
upsPhaseOutputMaxPower
upsPhaseOutputMinPower
upsPhaseOutputMaxPercentPower
upsPhaseOutputMinPercentPower
Resets the counter for the corresponding OID in the
[upsPhaseInput] and [upsPhaseOutput] groups. For
example, to reset the counter for the OID in the
[upsPhaseInput] category that reports the maximum input
current (upsPhaseInputMaxCurrent), SET to the OID with
that name in this [upsPhaseResetValues] category.