Technical information
Chapter 3:
How to Use OIDs for 3-Phase UPS Models
PowerNet MIB Reference Guide
26
[upsPhaseInput]
All of the OIDs in this category are read-only except for the upsPhaseInputName OID, a
{upsPhaseInputEntry} in the {upsPhaseInputTable}.
OID Task
upsPhaseNumInputs
{upsPhaseInputTable}
{upsPhaseInputEntry}
upsPhaseInputTableIndex
upsPhaseNumInputPhases
upsPhaseInputVoltageOrientation
upsPhaseInputFrequency
upsPhaseInputType
upsPhaseInputName
Use these read-only OIDs to obtain information about the
number of input feeds to the UPS, and information about
each of those feeds.
(upsPhaseInputPhaseTable)
{upsPhaseInputPhaseEntry}
upsPhaseInputPhaseTableIndex
upsPhaseInputPhaseIndex
upsPhaseInputVoltage
upsPhaseInputMaxVoltage
upsPhaseInputMinVoltage
upsPhaseInputCurrent
upsPhaseInputMaxCurrent
upsPhaseInputMinCurrent
upsPhaseInputPower
upsPhaseInputMaxPower
upsPhaseInputMinPower
Use the read-only OIDs to obtain the following
information for each input phase:
• The input voltage, input current, and input power now.
• The minimum and maximum value recorded for the
input voltage, input current, and input power since the
corresponding counters were reset by the OIDs in the
[upsPhaseResetValues] group.
The number of entries in the table depends on the sum of
the values reported for upsPhaseNumInputPhases in the
{upsPhaseInputTable} described above.