Technical information

Chapter 3:
How to Use OIDs for 3-Phase UPS Models
PowerNet MIB Reference Guide
26
[upsPhaseInput]
All of the OIDs in this category are read-only except for the upsPhaseInputName OID, a
{upsPhaseInputEntry} in the {upsPhaseInputTable}.
OID Task
upsPhaseNumInputs
{upsPhaseInputTable}
{upsPhaseInputEntry}
upsPhaseInputTableIndex
upsPhaseNumInputPhases
upsPhaseInputVoltageOrientation
upsPhaseInputFrequency
upsPhaseInputType
upsPhaseInputName
Use these read-only OIDs to obtain information about the
number of input feeds to the UPS, and information about
each of those feeds.
(upsPhaseInputPhaseTable)
{upsPhaseInputPhaseEntry}
upsPhaseInputPhaseTableIndex
upsPhaseInputPhaseIndex
upsPhaseInputVoltage
upsPhaseInputMaxVoltage
upsPhaseInputMinVoltage
upsPhaseInputCurrent
upsPhaseInputMaxCurrent
upsPhaseInputMinCurrent
upsPhaseInputPower
upsPhaseInputMaxPower
upsPhaseInputMinPower
Use the read-only OIDs to obtain the following
information for each input phase:
The input voltage, input current, and input power now.
The minimum and maximum value recorded for the
input voltage, input current, and input power since the
corresponding counters were reset by the OIDs in the
[upsPhaseResetValues] group.
The number of entries in the table depends on the sum of
the values reported for upsPhaseNumInputPhases in the
{upsPhaseInputTable} described above.