Technical information

Chapter 6:
[sPDUMasterStatusVM] Master Status OIDs
PowerNet MIB Reference Guide
47
[sPDUMasterStatusVM] Master Status OIDs
The [sPDUMasterStatusVM] category has a read-only OID and a tabled set of read-only OIDs that provide information
on the status of the MasterSwitch VM unit.
OID Information Reported
sPDUMasterStatusVMTableSize
The number of MasterSwitch VM units.
{sPDUMasterStatusVMTable}
{sPDUMasterStatusVMEntry}
sPDUMasterStatusVMIndex
sPDUMasterStatusVMName
sPDUMasterStatusVMCommandPending
sPDUMasterStatusVMOverloadCondition
sPDUMasterStatusVMLowLoadCondition
sPDUMasterStatusVMCurrentLoad
sPDUMasterStatusVMMaxLoad
sPDUMasterStatusVMOutletCount
sPDUMasterStatusVMRebootDuration
Information about the status of a specified MasterSwitch VM unit.
The index to the MasterSwitch VM unit
s entry (read-only).
The name of the MasterSwitch VM unit (read-only). (You use the
sPDUMasterConfigVMName OID to define this name.)
One of the following:
- commandPendingMasterTrueVM (1) if the MasterSwitch VM
unit has a pending command on any of its outlets.
- commandPendingMasterFalseVM (2) if there are no pending
commands.
One of the following:
- overloadConditionTrueVM (1) if the
sPDUMasterConfigVMHighLoadWarningThreshold OID is
violated.
- overloadConditionFalseVM (2) if the
sPDUMasterConfigVMHighLoadWarningThreshold OID is not
violated.
One of the following:
- lowLoadConditionTrueVM (1) if the
sPDUMasterConfigVMLowLoadWarningThreshold OID is
violated.
- lowLoadConditionFalseVM (2) if the
sPDUMasterConfigVMLowLoadWarningThreshold OID is not
violated.
The total power being used by the attached equipment as a
percentage of full load.
The total power, in Amperes, that the MasterSwitch VM unit can
provide.
The number of controllable outlets for the MasterSwitch VM unit.
The largest sPDUOutletConfigVMRebootDuration OID time for
the MasterSwitch VM unit