Technical information
Chapter 7:
[sPDUOutletControlMSP] Outlet Control OIDs
PowerNet MIB Reference Guide
55
[sPDUOutletControlMSP] Outlet Control OIDs
The [sPDUOutletControlMSP] category has a tabled set of OIDS that provide information on the outlets at a
MasterSwitch Plus unit and provide commands to control individual outlets.
OID Task
{sPDUOutletControlMSPTable}
{sPDUOutletControlMSPEntry}
sPDUOutletControlMSPIndex
sPDUOutletControlMSPName
sPDUOutletControlMSPOutletIndex
sPDUOutletControlMSPOutletName
sPDUOutletControlMSPOutletCommand
Control a specified outlet. (The
sPDUMasterStatusMSPOutletCount OID identifies the number
of table entries.)
• The index to the MasterSwitch Plus unit’s entry (read only).
• The name of the MasterSwitch Plus unit (read only) (You use the
sPDUMasterConfigMSPName OID to define this name).
• The outlet number (read only).
• The name of the MasterSwitch Plus unit (read only) (You use the
sPDUOutletConfigMSPallOutletName OID to define this
name).
• Use a GET to obtain the outlet state.
- immediateOnMSP (1) if the outlet is on.
- immediateOffMSP (3) if the outlet is off.
Use a SET to perform any of the following.
- immediateOnMSP (1): Immediately turn on the outlet.
- delayedOnMSP (2): Turn on the outlet after the time specified
by the sPDUOutletConfigMSPgsPowerOnDelay OID.
- immediateOffMSP (3): Immediately turn off the outlet.
- gracefulRebootMSP (4): Cause the outlet to wait for device
confirmation (if applicable), then turn off after the time
specified by the sPDUOutletConfigMSPgsPowerOffDelay
OID, and then turn on after the time specified by the
sPDUOutletConfigMSPgsRebootDuration OID
- immediateRebootMSP (5): Immediately reboot the outlet.
- gracefulShutdownMSP (6): Cause the outlet to wait for device
confirmation (if applicable), then turn off after the time
specified by the sPDUOutletConfigMSPgsPowerOffDelay
OID. The outlet will turn on again after waiting both the time
specified by the sPDUOutletConfigMSPgsRestartDelay OID
and the time specified by the
sPDUOutletConfigMSPgsPowerOnDelay OID
- overrideBatCapThreshMSP (7): Cause the outlet to ignore the
battery capacity threshold and turn on after the time specified by
the sPDUOutletConfigMSPgsPowerOnDelay OID.
- cancelPendingCommandMSP (8): Cancel any pending
command on the outlet.