Technical information

Chapter 7:
[sPDUOutConfigMSPgs] Outlet Configuration OIDS
PowerNet MIB Reference Guide
57
OID Task
{sPDUOutletConfigMSPgsTable}
{sPDUOutletConfigMSPgsEntry}
sPDUOutletConfigMSPgsIndex
sPDUOutletConfigMSPgsName
sPDUOutletConfigMSPgsOutletIndex
sPDUOutletConfigMSPgsOutletName
sPDUOutletConfigMSPgsOutletCtrlMode
sPDUOutletConfigMSPgsDeviceConfirm
sPDUOutletConfigMSPgsLowBattWarning
sPDUOutletConfigMSPgsLowBattMult
sPDUOutletConfigMSPgsRestartDelay
sPDUOutletConfigMSPgsPowerOnDelay
sPDUOutletConfigMSPgsPowerOffDelay
sPDUOutletConfigMSPgsBattCapThresh
sPDUOutletConfigMSPgsRebootDuration
View and configure a specified outlet for Graceful Shutdown mode. (The OID
sPDUMasterStatusMSPOutletCount identifies the number of table entries.)
The index to the MasterSwitch Plus units entry (read only).
The name of the MasterSwitch Plus unit (read only). (You use the
sPDUMasterConfigMSPName OID to define this name).
The outlet number (read only)
The name of the outlet (read only). (You use the
sPDUOutletConfigMSPallOutletName OID to define this name).
The control mode of the outlet, as defined by the
sPDUOutletConfigMSPallOutletCtrlMode OID:
- modeGracefulShutdown: (1): In Graceful Shutdown Control Mode.
- modeAnnunciator (2): In Annunciator Mode.
Define whether the outlet waits for shutdown confirmation before turning off.
- deviceConfirmNo (1): Do not wait for confirmation.
- deviceConfirmYes (2): Wait for confirmation.
Define how long this outlet will wait before beginning its turn-off sequence
after the UPS switches to battery operation.
- -2: Do not turn off the outlet.
- -1: Begin the turn-off sequence based on remaining runtime.
- 0: Begin the turn-off sequence at low battery warning.
- 1 to 9999 intervals of 6 seconds each. Begin the turn-off sequence after the
specified number of intervals (e.g. 5994 = 1 hour, 39 minutes, 54 seconds).
Define a multiplier value for this outlet that enables load shedding, i.e. as
UPS battery runtime decreases, outlets turn off in stages, so that power is
maintained to your most important equipment for as long as possible.
- 1 to 7: Unless the sPDUOutletConfigMSPgsLowBattWarning OID is -2,
turn off this outlet when the remaining UPS battery runtime is less than this
value multiplied by the low battery warning time received from the UPS.
See Example of a Load-Shedding Configuration (next page).
- When the sPDUOutletConfigMSPgsLowBattWarning OID is set to -2,
any value specified for this OID is ignored.
Define how long the outlet will wait between turning off and turning on after
graceful shutdown.
- -1: The outlet never turns on after a graceful shutdown.
- 0 to 9999 intervals of 6 minutes each. Begin the outlets turn-on sequence
after the specified number of intervals (e.g. 9999 = 999 hours, 54 minutes.
Define the number of seconds the outlet will wait before turning on after the
UPS returns to online operation.
- -1: Never turn on the outlet after the UPS returns to online operation.
- 0 to 9999 seconds (0 seconds to 2 hours, 46 minutes, 39 seconds).
Define the number of seconds the outlet will wait after the server shuts down
until the outlet begins its turn-off sequence. Allowed values are 0 to 9999.
Define the percentage of full battery capacity needed before the outlet is
allowed to turn on.
Define the number of seconds the outlet will wait after the it turns off until it
turns on during a reboot. Allowed values are 0 to 9999.