Technical information
Chapter 7:
[sPDUOutConfigMSPgs] Outlet Configuration OIDS
PowerNet MIB Reference Guide
59
If the UPS’s Low Battery Signal Time is set to 25 minutes, and the UPS switches to battery operation with 60 minutes
of Runtime Remaining, the outlets will turn off as follows:
• Outlet 1 will begin its turn-off sequence immediately, without waiting the 6-minute Low Battery Warning,
because the Runtime Remaining of 60 minutes is already less than 175 minutes (Low Battery Multiplier x the
Low Battery Signal Time of the UPS).
• Outlet 2 will begin its turn-off sequence immediately, without waiting the 6-minute Low Battery Warning,
because the Runtime Remaining of 60 minutes is already less than 150 minutes (Low Battery Multiplier x the
Low Battery Signal Time of the UPS).
• Outlet 3 will begin its turn-off sequence after 10 minutes, when the Runtime Remaining is depleted to less 50
minutes (Low Battery Multiplier x the Low Battery Signal Time of the UPS). The full 12-minute Low Battery
Warning will not yet have expired.
• Outlet 4 will begin its turn-off sequence when the 7-minute Low Battery Warning expires, instead of waiting
until after 10 minutes when the Runtime Remaining would be depleted to less than 50 minutes (Low Battery
Multiplier x the Low Battery Signal Time of the UPS).
• Outlet 5 will begin its turn-off sequence immediately because the 60-minute Runtime Remaining is already less
than 75 minutes (Low Battery Multiplier x the Low Battery Signal Time of the UPS).
• Outlet 6 will begin its turn-off sequence after 10 minutes, when the Runtime Remaining is depleted to less than
50 minutes (Low Battery Multiplier x the Low Battery Signal Time of the UPS).
• Outlet 7 will begin its turn-off sequence after 35 minutes, when the Runtime Remaining is depleted to less than
25 minutes (Low Battery Multiplier x the Low Battery Signal Time of the UPS).
• Outlet 8 will not begin a turn-off sequence because the value defined for the
Low Battery Warning indicates that
the outlet should never turn off. The 75 minutes calculated as Low Battery Multiplier x the Low Battery Signal
Time of the UPS is ignored.