Technical information
Chapter 7:
[sPDUOutConfigMSPannun] Outlet Configuration OIDS
PowerNet MIB Reference Guide
60
[sPDUOutConfigMSPannun] Outlet Configuration OIDS
The [sPDUOutConfigMSPannun] category has a has a tabled set of OIDS to configure individual outlets in
Annunciator mode.
OID Task
{sPDUOutletConfigMSPannunTable}
{sPDUOutletConfigMSPannunEntry}
sPDUOutletConfigMSPannunIndex
sPDUOutletConfigMSPannunName
sPDUOutletConfigMSPannunOutletIndex
sPDUOutletConfigMSPannunOutletName
sPDUOutletConfigMSPannunOutletCtrlMode
sPDUOutletConfigMSPannunInitialState
sPDUOutletConfigMSPannunAlarmActionDly
View and configure individual outlets in Annunciator Mode.
The OID sPDUMasterStatusMSPOutletCount contains the
number of entries in this table.
• The index to the MasterSwitch Plus unit’s entry (read only).
• The name of the MasterSwitch Plus unit (read only). (You
use the sPDUMasterConfigMSPName OID to define this
name).
• The outlet number (read only)
• The name of the outlet (read only). (You use the
sPDUOutletConfigMSPallOutletName OID to define this
name).
• The control mode of the outlet, as defined by the OID
sPDUOutletConfigMSPallOutletCtrlMode:
- modeGracefulShutdown: (1): The outlet is in Graceful
Shutdown control mode.
- modeAnnunciator (2): The outlet is in Annunciator
control mode.
• Define the initial (default) state of the outlet:
- initialStateOff (1): The outlet defaults to off when in the
non-alarmed condition.
- initialStateOn (2): The outlet defaults to on when in the
non-alarmed condition.
• Define the time in seconds that an alarm from an
Environmental Monitor must continue before it causes an
alarm condition. Allowed values are 0 to 9999 seconds (2
hours, 46 minutes, 38 seconds) If the alarm is disabled for the
outlet, as described in [sPDUOutConfigMSPmups] Outlet
Configuration OIDs, this OID’s value is ignored.