Technical information

Chapter 8:
[atsControl] Control OIDs
PowerNet MIB Reference Guide
67
[atsControl] Control OIDs
The [atsControl] category has two read-write OIDs that provide commands to control the resetting of the Automatic
Transfer Switch and the clearing of all its alarms.
[atsConfig] Configuration OIDs
The [atsConfig] category has seven read-write OIDs that provide commands to configure the Automatic Transfer
Switch.
OID Task
atsControlResetATS Setting this variable determines whether the Automatic Transfer Switch
performs a reset when power is applied.
none (1): Does not perform a reset.
reset (2): Performs a power-on reset.
atsControlClearAllAlarms Setting this variable determines whether all alarms in the Automatic
Transfer Switch are cleared.
none (1): Does not clear alarms.
clear (2): Clears all alarms.
OID Task
atsConfigProductName A character string that names the Automatic Transfer Switch.
atsConfigPreferredSource The preferred source of power when both sources are functioning properly:
source A (1), source B (2), or none (3)
atsConfigFrontPanelLockout Determines whether you can set source preference from the Automatic
Transfer Switchs front panel:
disableFrontPanel (1): Disables the capability to set source preference for the
Automatic Transfer Switch from its Front Panel. To re-enable this capability,
you must use the serial interface of the Automatic Transfer Switch.
enableFrontPanel (2): Allows setting source preference for the Automatic
Transfer Switch from its Front Panel.
atsConfigVoltageSensitivity Defines the sensitivity of the Automatic Transfer Switch to changes in voltage:
high (1): Provides the best protection
low (2): Allows the Automatic Transfer Switch to tolerate frequent small line
voltage changes.
atsConfigTransferVoltageRange Defines the range of acceptable voltage from a power source: wide (1),
medium (2), or narrow (3).
If the voltage from the selected input source is not within this range, the
Automatic Transfer Switch switches to the alternate power source.
atsConfigCurrentLimit The threshold (in Amps) at which an Over Current Alarm is generated.
atsConfigResetValues Resets the configuration of the Automatic Transfer Switch to its default values.
do not reset (1) or reset (2).