[atsStatusInput] Input OIDs
PowerNet MIB Reference Guide
70
[atsStatusInput] Input OIDs
The [atsStatusInput] category has an OID and two tabled set of OIDS that provide information on the Automatic
Transfer Switchs input feeds and their phases. All OIDs in this category are read-only except atsInputName, which is
read-write.
OID Information Reported
atsNumInputs The number of input feeds to this device. This number defines the number of rows
in atsInputTable.
{atsInputTable}
{atsInputEntry}
atsInputTableIndex
atsNumInputPhases
atsInputVoltageOrientation
atsInputFrequency
atsInputType
atsInputName
A tabled set of OIDs providing the following information for each input feed:
The input feed identifier.
The number of input phases used in this device. This number defines the number
of rows in atsInputPhaseTable.
The input voltage orientation:
unknown (1): Unknown for this source.
singlePhase (2): Phase 1 voltage is between Phase 1 and neutral.
splitPhase (3): Phase 1 voltage is between Phase 1 and Neutral; phase 2
voltage is between Phase 2 and Neutral; and phase 3 voltage is between Phase
1 and Phase 2.
threePhasePhaseToNeutral (4): Phase 1 voltage is between Phase 1 and
Neutral; phase 2 voltage is between Phase 2 and Neutral; and phase 3 voltage is
between Phase3 and Neutral.
threePhasePhaseToPhase (5): Phase 1 voltage is between Phase 1 and Phase
2; phase 2 voltage is between Phase 2 and Phase 3; and phase 3 voltage is
between Phase 3 and Phase 1.
The input frequency in Hz, or -1 if it is unsupported by this source.
The input type.
The name given to this input. This value is read-write.