Technical information
Chapter 8:
[atsStatusInput] Input OIDs
PowerNet MIB Reference Guide
71
{atsInputPhaseTable}
{atsInputPhaseEntry}
atsInputPhaseTableIndex
atsInputPhaseIndex
atsInputVoltage
atsInputMaxVoltage
atsInputMinVoltage
atsInputCurrent
atsInputMaxCurrent
atsInputMinCurrent
atsInputPower
atsInputMaxPower
atsInputMinPower
A tabled set of OIDs providing the following information for each input phase.
Parameters that are unsupported by your model of the Automatic Transfer Switch
return –1.
• The input identifier.
• The input phase identifier.
• The input voltage in VAC.
• The maximum input voltage in VAC recorded since the last time this value was
read or reset by atsStatusResetMaxMinValues.
• The minimum input voltage in VAC recorded since the last time this value was
read or reset by atsStatusResetMaxMinValues.
• The input current in Amps.
• The maximum input current in Amps recorded since the last time this value was
read or reset by atsStatusResetMaxMinValues.
• The minimum input current in Amps recorded since the last time this value was
read or reset by atsStatusResetMaxMinValues.
• The input power in Watts.
• The maximum input power in Watts recorded since the last time this value was
read or reset by atsStatusResetMaxMinValues.
• The minimum input power in Watts recorded since the last time this value was
read or reset by atsStatusResetMaxMinValues
OID Information Reported