Technical information
Chapter 8:
[atsStatusOutput] Output OIDs
PowerNet MIB Reference Guide
72
[atsStatusOutput] Output OIDs
The [atsStatusOutput] category has a read-only OID and two tabled set of read-only OIDS that provide information on
the Automatic Transfer Switch’s output feeds and their phases.
OID Information Reported
atsNumOutputs The number of output feeds to this device.This number defines the number of
rows in atsOutputTable.
{atsOutputTable}
{atsOutputEntry}
{atsPhaseOutputEntry}
atsOutputTableIndex
atsNumOutputPhases
atsOutputVoltageOrientation
atsOutputFrequency
A tabled set of OIDs providing the following information for each output.
• The output identifier.
• The number of output phases used in this device. This number defines the
number of rows in atsOutputPhaseTable.
• The output voltage orientation:
unknown (1): Unknown for this Automatic Transfer Switch.
singlePhase (2): Phase 1 voltage is between Phase 1 and neutral.
splitPhase (3): Phase 1 voltage is between Phase 1 and Neutral; phase 2
voltage is between Phase 2 and Neutral; and phase 3 voltage is between Phase
1 and Phase 2.
threePhasePhaseToNeutral (4): Phase 1 voltage is between Phase 1 and
Neutral; phase 2 voltage is between Phase 2 and Neutral; and phase 3 voltage
is between Phase3 and Neutral.
threePhasePhaseToPhase (5): Phase 1 voltage is between Phase 1 and Phase
2; phase 2 voltage is between Phase 2 and Phase 3; and phase 3 voltage is
between Phase 3 and Phase 1.
• The output frequency in Hertz, or –1 if it is unsupported by this Automatic
Transfer Switch.