Managing the Expansion Unit
Outlet Properties Menu
continued
Graceful
Shutdown menu
items, continued
Continued on next page
Item Definition Available Settings
Restart Delay
The delay between an outlet shutting
off due to a Graceful Shutdown and
the outlet being restarted.
Range
:
0–999:54
Note: Time is rounded
down by 6-minute
intervals
Power Off
Delay
The time from the triggering event
(such as a server confirming a
shutdown) until the outlet is turned off.
Range
:
0–2:46:39
Power On
Delay
Determines the time interval between
the triggering event and the outlet
being turned on.
Range
:
0–2:46:39
Reboot
Duration
The delay between the outlet shutting
off because of Reboot and the outlet
restarting.
Range
: 0–2:46:39
Battery
Capacity
Threshold
Sets the minimum percentage of
Battery Capacity required of the UPS
before an outlet can be turned on.
Range
:0–100%
Enable/
Disable UPS
Alarms
Environment Alarm Masks: Indicates
whether or not an outlet will react to a
specific Environment alarm.
Enabled and disabled for
each of the twelve
Environmental alarms.
Select Another
Outlet
Allows you choose an another outlet to configure.
Alarm Action
Delay
Theamountoftimethatan
Environment alarm must be asserted
before the unit reacts to the alarm.
Range:
0–2:45:00