User`s guide
–54–
Managing the Expansion Unit
Outlet Properties Menu
continued
Annunciator menu
items
Environmental
Monitoring Card
menu
.
Item Definition Available Settings
Outlet Name Identifies each outlet. 20 characters maximum
Outlet Control
Mode
Establishes mode for associated outlet.
Graceful Shutdown or
Annunciator
Initial State Defines the initial state of the outlet.
Off
On
Alarm Action
Delay
TheamountoftimethatanEnvironment
alarm must be asserted before the unit
reacts to the alarm.
Range
:0–2:45:00
Enable/Disable
UPS Alarms
Environment Alarm Masks: Indicates
whether or not an outlet will react to a
specific Environment alarm.
Settings are enabled and
disabled for each of the 12
Environmental Monitoring
Card alarms.
Select Another
Outlet
Allows you choose an another outlet to configure.
Item Description
Tem p ( Ce l ci u s)
Displays the current ambient temperature reading of each attached
probe. Temperature is displayed in ##.## degrees Celsius.
Humidity
Displays the current relative humidity reading of each attached
probe. Humidity is displayed in ###.#% relative humidity.
Low Limit
Allows you to disable or set the low alarm threshold for temperature
and humidity for each probe. Temperature threshold is in degrees
Celsius and humidity is in percent relative humidity. If alarm limits
are exceeded, an alarm will be asserted to all outlets whose
Enable/Disable Alarm settings for that alarm are set to Enabled.
High Limit
Allows you to disable or set the low alarm threshold for temperature
and humidity for each probe. Temperature threshold is in degrees
Celsius and humidity is in percent relative humidity. If alarm limits
are exceeded, an alarm will be asserted to all outlets whose
Enable/Disable Alarm settings for that alarm are set to Enabled.
Disable All
Alarms
Allows you to control Environmental Monitoring Card operation.
The options are:
Yes
: all alarm limits are set to Disabled. MasterSwitch plus will
ignore all Environment alarms.
No
: all alarm limits are reset to previous configuration.