User`s guide
–55–
MasterSwitch plus
Product Information
Accessories Affected by MasterSwitch
plus
PowerChute Plus
The Scheduled Shutdown and Shut Down System Now commands are
available in PowerChute Plus to perform actions on the server
connectedtoOutlet
#1
of MasterSwitch plus. However, the Shut Down
System Now command will turn off Outlet
#1
and will require you to turn
it on through the User Interface to restart. Additional settings affected
include those listed in the following table.
Management
Peripherals
UPS
control commands available with
APC
accessories are not
supportedwhenusedwithMasterSwitchplus. Therefore, on-demand
operation through
APC
accessories is not supported at this time.
PowerChute Plus Setting Relationship to MasterSwitch plus
UPS
Low Battery Signal Time
Multiplied by the
UPS
Low Battery Multiplier for
each outlet of MasterSwitch plus. See page 32
for more information.
UPS
Turn Off Delay
Overridden by the Power Off Delay for each
outlet of MasterSwitch plus. See page 31 for
more information.
UPS
Wakeup Delay Time
Overridden by the Power On Delay for each
outlet in MasterSwitch plus. See page 31.
UPS
Wakeup Delay
(Capacity)
Overridden by the Battery Capacity Threshold
foreachoutletinMasterSwitchplus.See
page 32 for more information.