Specifications

Chapter 2. APC hardware and software background 5
Table 1. Technical specifications
The typical SU2200RMXLINET on-battery run times versus VA load, in minutes
(with SU48RMXLBP) are as follows:
Table 2. Run time SU2200RMXLINET
The UPS is furnished with one input line cord terminated with a CEE7/7 plug and
three 1.8 m long output cords appropriate for connection to equipment with 10
Amp IEC320 appliance receptacles. There is also a set of 19'' rack mounting run
time in the package, together with L-bracket mounts, which adjust for different
depth racks and support the weight of the UPS, allowing the unit to slide in place
and for easy securing of the rack mount ears.
VA/W ratings Maximum 2200 VA or 1600 W
Type of external battery
packs
SU48RMXLBP (8 x 12 V DC and 17 Ah. Nominal system
voltage 48 V DC)
Dimensions: UPS Height 22.2 cm
(5U) x width 48.3 cm x depth 45.1 cm.
(Depth is measured from front of bezel to back of chassis, with
a half-inch allowance for screws and outlets.)
Dimensions: battery pack Height 17.8 cm x width 48.3 cm x depth 45.7cm
Maximum input current 12 Amps (for nominal line voltages indicated and load
p.f. ~ 0.7 includes load current)
Input resettable circuit
breaker rating
20 Amps
Input wiring devices IEC 320 C20 16 Amp outlet (1x)
Hardwiring input option Not available
Output wiring devices IEC 320 C19 16 Amp outlet (1x)
IEC 320 C13 10 Amp outlet (8x)
Software monitoring and
management
940-0024C black APC serial cable (smart-signaling mode)
Software compatible with
the UPS
PowerChute PLUS 5.1 for Windows NT
PowerChute PLUS 5.2 for Windows NT/2000
Replacement battery
cartridge
RBC11
Load internal
battery
1battery
pack
2battery
packs
3battery
packs
4battery
packs
5battery
packs
1000VA
25
120 225 335 440 550
1200VA
20
91 180 270 360 450
1400VA
16
73 150 225 300 375
1600VA
13
60 120 185 250 315
1800VA
11
52 105 160 220 280
2000VA
9
44 87 140 190 245
2200VA
8