Specifications
20 Implementing UPS Configurations with Microsoft Cluster Server
• Run a command file (an external executable file)
• Page users
• Send e-mail to notify users that the event occurred
Figure 12. PowerChute PLUS Event Actions Menu (Go to Main Menu-Configuration-Event Actions)
2.4.1.4 Smart UPS events
The critical events monitored are as follows:
• UPS On Battery
The UPS has switched to battery power due to one of the following situations:
– High input line voltage
– Brownout
– Blackout
– Small momentary power sag
– Small momentary power spike
– Deep momentary power sag
– Large momentary power spike
– Simulated power failure
RECOMMENDED ACTION: Run the command file UPS.CMD to either move
or set the Cluster Groups offline. This script is described in Chapter 4, “The
command file UPS.CMD” on page 67.
• Low Battery Condition
The amount of UPS run time remaining has reached the Low Battery Signal
Time. For example, configuring the Low Battery Signal Time to 10 minutes
causes PowerChute PLUS to initiate low battery shutdown when the UPS is
on battery and 10 minutes of run time remain.
RECOMMENDED ACTION: Run the command file UPS.CMD to either move
or set the Cluster Groups offline. This script is described in Chapter 4, “The
command file UPS.CMD” on page 67.