Specifications
© Copyright IBM Corp. 2001 1
Chapter 1. The problem
How can servers be protected against power failures? Usually redundant power
supplies and redundant power cords connected to different power lines are used
for basic protection.
The failure of one of these components does not affect the operation of the
server. To protect the system against a complete power loss, an uninterruptible
power supply (UPS) is required. If software such as PowerChute PLUS is
installed on the system and a communication link is set between the UPS and the
server, PowerChute PLUS can stop the applications and shut down the operating
system.
Figure 1. UPS with one server
For larger solutions such as a Microsoft Cluster Server (MSCS) configuration, a
single UPS may not provide sufficient protection. The run-time capacity of one
UPS is inadequate in most cases for two servers with shared storage.
Additionally, one UPS is a single point of failure. Thus, you need two or more
UPS units. However, in an MSCS environment with one or two UPS units you
have certain problems:
• Application handling: In an MSCS environment you cannot simply stop an
application; the cluster application must be set to offline with the cluster
administration tool. If the application is stopped by normal procedures (such
as PowerChute PLUS’s Application Shutdown or application-specific stop
procedure), then the application would be considered as failed and restarted
by the cluster resource monitor.
• Server status: If a power loss occurs on one server, a communication about
the status of the other server is required. If only the local server is affected by
the power loss, then it makes sense to move all cluster resources from this
node to the surviving one. Otherwise, if no other node is available or if the
other node will also shut down, then the resources must be set to offline.
• Server power cabling: How are power cables connected? Some servers
have a N+1 redundancy in power supplies. If you connect a server with three
power supplies and three power cords to two power circuits, you have at least
two power supplies on the same circuit. It is possible that this circuit will fail.
With the one remaining power supply, the server will not work. In the case of a
server with two power cords, you could try to connect them to different UPS
units. But then you have the communication problem as described below.
Server
UPS
Communication
Smart signaling cable
Power
Power
Power










