Interpreting alarms
The Battery Management System can generate Major or Minor alarms.
•A Major alarm requires immediate action to ensure that the batteries
are able to provide back-up power.
•A Minor alarm indicates a condition that is not likely to result in the
batteries being unable to provide back-up power, but could develop
into a major alarm, or could prevent the detection of a major alarm.
Each alarm type will close an associated normally-open alarm relay. The
alarm relays can be connected to a device that monitors normally-open and
normally-closed sensors.
Sensor calibration. The Battery Management System is in sensor
calibration mode. You can set this mode by setting DIP switch 4 (on each
sensor) to On. The Battery Management System will then obtain a new
zero value. The LEDs will flash at a rate of once per second while the
Battery Management System is in this mode. After five flashes, the sensor
is calibrated.
C
aut
i
on
Do not perform sensor calibration while there is current flowing
through the sensor. Remove the sensor from the battery cable
before performing a sensor calibration.
Possible Causes Corrective Action
The Battery Management
System is in sensor
calibration mode.
• Set the current sensor’s DIP switch number four to Off.
S
ee a
l
so
See the Installation and Quick-Start Manual for instructions
on how to calibrate the sensors.