User Manual Racks and Accessories NetShelter SV AR2200, AR2201, AR2280, AR2400, AR2400FP1, AR2401, AR2407, AR2480, AR2487, AR2500, AR2501, AR2507, AR2580, AR2587 990-4823A-001 Publication Date: 2013
This manual is available in English on the APC Web site (www.apc.com). Dieses Handbuch ist in Deutsch auf der APC Webseite (www.apc.com) verfügbar. Este manual está disponible en español en la página web de APC (www.apc.com). Ce manuel est disponible en français sur le site internet d’APC (www.apc.com). Questo manuale è disponibile in italiano sul sito web di APC (www.apc.com). ᮏ࣐ࢽࣗࣝ㸺ྛᅜࡢゝㄒᑐᛂࡍࡿ㸼ࡣ APC ࢙࢘ࣈࢧࢺ (www.apc.
Disclaimer The information presented in this manual is not warranted by Schneider Electric to be authoritative, error free, or complete. This publication is not meant to be a substitute for a detailed operational and site specific development plan. Therefore, Schneider Electric assumes no liability for damages, violations of codes, improper installation, or any other problems that could arise based on the use of this publication.
Contents Disclaimer . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 Please Note: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 General Information ........................................................ 1 Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 Safety . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Customize the Cabinet.................................................. 10 Reverse the Front Door . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10 Side Panels . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12 Remove and install side panels . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12 Rear Doors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12 Removal. . . . . . . . . . . . . . . . .
General Information Introduction The NetShelter® SVcabinet is for storage of industry-standard (EIA/ECA-310), 19-inch rack-mount hardware, which includes servers and voice, data, networking, internetworking, and Schneider Electric power protection equipment. This manual provides installation and customization instructions for the following: • NetShelter SV 42 U, 600 mm (23.6 in.) wide, 1000 mm (39.4 in.) deep cabinet (AR2200) • NetShelter SV 42 U, 600 mm (23.6 in.) wide, 1000 mm (39.4 in.
Safety Important Safety Information Read the instructions carefully to become familiar with the equipment before trying to assemble, operate, service or maintain it. The following special messages may appear throughout this manual or on the equipment to warn of potential hazards or to call attention to information that clarifies or simplifies a procedure.
Receiving and Unpacking NOTICE Schneider Electric is not responsible for damage sustained during shipment of this product. Inspection Upon receipt, inspect the package and contents for damage. Verify the contents are complete. Report missing contents, damage, or other problems immediately to Schneider Electric or your Schneider Electric reseller. Keep all packaging for inspection if damage is found. Overview Introduction Tools Safety and handli ng Please Recycle The shipping materials are recyclable.
Unpacking WARNING TIP HAZARD This cabinet is easily tipped. Use extreme caution when unpacking or moving. • Use at least two people to unpack and move the cabinet. • Before moving the cabinet on its casters, load 158 kg (350 lbs) of equipment into the bottom of the cabinet for extra stability. • When moving on its casters, make sure the leveling feet are up and push the cabinet from the front or rear. Failure to follow these instructions can result in death, serious injury, or equipment damage. 1.
ns2118a Component Identification Item Description Roof Rear Frame Grounding wire Rear Split Doors Side Panels Horizontal Side Braces Accessory Mounting Brackets Base Qty Item 1 1 3 2 2 6 4 1 Description Leveling Feet Casters Front Frame Vertical Mounting Flanges Door and Side Panel Keys Door Handles Front Door Roof/Base Access Panels NetShelter SV User Manual Qty 4 4 1 4 2 2 1 2 5
Equipment Installation Hardware Plastic cup washers (30) M6 x 16 Phillips Cage nuts (30) head screws (30) Joining Brackets for M5 x 12 screws (4) 24 in.
Cabinet Installation Moving the Cabinet WARNING TIP HAZARD This cabinet is easily tipped. Use extreme caution when unpacking or moving. • Use at least two people to unpack and move the cabinet. • Before moving the cabinet on its casters, load 158 kg (350 lb) of equipment into the bottom equipment mounting space of the cabinet for extra stability. • When moving on its casters, make sure the leveling feet are up and push the cabinet from the front or rear.
Joining Cabinets Cabinets can be joined with or without side panels installed to provide for alignment and some stability. The cabinets are shipped with pre-installed joining brackets for 600 mm centers. To join on 24 in. centers, the cabinet is provided with 24 in. joining brackets in the hardware bag. WARNING TIP HAZARD Joining cabinets provides limited stability. Ensure the cabinet is secured to the floor before installing equipment.
Secure the Cabinet NOTICE Bolt-down brackets secure the cabinet to the pallet during shipment. Remove them from the cabinet and pallet and save them to secure the cabinet to the floor during installation. WARNING TIP HAZARD Secure the cabinet to the floor before installing equipment. Failure to follow these instructions can result in serious injury or equipment damage.
Customize the Cabinet Reverse the Front Door You can reverse the front door so that the door is hinged on the opposite side. ns2006a 1. Remove the handle using the Torx T30/#2 Phillips wrench (provided). ns2007a 2. Unfasten the ground wire from the cabinet and door, then remove the door. ns2008a 3. Rotate and reinstall the door to the opposite side. Remove any plastic hole plugs and reinstall the ground wire to the door and cabinet.
ns1766b 4. Remove and reinstall the latch and washer oriented as shown using a Torx T30/#2 Phillips wrench. The washer is rotated 90 degrees from its original orientation, and the latch is rotated 180 degrees. ns2009a 5. Reinstall the handle to the door. Torque the screws to 28 - 30 in-lb (3.2 - 3.4 N-m).
Side Panels ns2060a Remove and install side panels Rear Doors Removal 1. Disconnect the grounding wires attached to the rear doors at the connector. ns2065b x2 2. Remove the left and right rear doors by pulling the top hinge pin down to release the pin from the hole securing it to the frame. x2 ns2087a 3. Lift the door to remove the bottom hinge pin from the hole in the cabinet base.
Installation 1. Install the left and right rear doors by aligning the bottom hinge pin to the hole in the cabinet base. x2 ns2064a 2. Pull the top hinge pin down, align with the hole in the roof, then release. 3. Connect the grounding wires.
Equipment Installation NOTICE NetShelter SV cabinets are intended for use with Listed equipment. If you install un-Listed equipment, you should evaluate the safety of your configuration. Adjust Vertical Mounting Flanges ns2013a Vertical mounting flanges come factory-installed in the proper location for use with rack-mountable equipment.
Installation 1. Use the Torx T30/#2 Phillips wrench (provided) to adjust a vertical mounting flange. Remove the T30 screws at the top, middle, and bottom of the vertical mounting flange. Save the screws for adjustment and reinstallation in the new position. 800 mm cabinet ns2014a 600 mm cabinet CAUTION STABILITY HAZARD When adjusting vertical mounting flanges, ensure that no equipment is installed on the vertical mounting flanges.
ns2015a 2. Move the mounting flange to the desired location and reinstall the T30 fastener at the top, middle and bottom to secure the vertical mounting flange. ns2016a 3. Perform the vertical mounting flange adjustment to the opposite side of the cabinet. Ensure that the same mounting position is used at the top, middle and bottom. Torque to 28 - 30 in-lb (3.2 3.4 N-m). NOTICE Verify that all Vertical Mounting Flanges are properly aligned before installing equipment in place.
Installing Equipment WARNING TIP HAZARD This cabinet is easily tipped. Follow the precautions below during and after equipment installation. • Make sure you have secured the cabinet to the floor before installing equipment. • Install the heaviest equipment first toward the bottom of the cabinet to prevent the cabinet from becoming top-heavy.
Cable Management Route, secure, and organize cables using the multiple cable access openings on the cabinet roof, sides, and bottom, the accessory mounting brackets included with the cabinet, plus the variety of cable management accessories available. Adjust Vertical 0 U Accessory Mounting Brackets The vertical 0 U accessory mounting brackets (four included) provide toolless mounting capabilities for Schneider Electric Rack Power Distribution Units (PDUs) and cable management.
Specifications 42 U Cabinets AR2200 AR2400 AR2401 Height 2057 mm (81.0 in.) 2057 mm (81.0 in.) 2057 mm (81.0 in.) Width 600 mm (23.6 in.) 600 mm (23.6 in.) 600 mm (23.6 in.) Depth 1000 mm (39.4 in.) 1060 mm (41.7 in.) 1060 mm (41.7 in.) Net weight 108.8 kg (239.9 lb) 112.2 kg (247.4 lb) 85.0 kg (187.
42 U Cabinets, continued AR2500 AR2280 Height 2057 mm (81.0 in.) 2057 mm (81.0 in.) Width 600 mm (23.6 in.) 800 mm (31.5 in.) Depth 1200 mm (47.2 in.) 1000 mm (39.4 in.) Net weight 121.3 kg (267.4 lb) 126.7 kg (279.3 lb) Total open area front door 778 176 mm2 (1,206 in2) 1 137 330 mm2 (1,763 in2) Total open area rear door 805 637 mm2 (1,2492) 1 171 657 mm2 (1,816 in2) Open area per U front door 18 528 mm2 (28.7 in2) 27 079 mm2 (42.0 in2) Open area per U rear door 19 182 mm2 (29.
42 U Cabinets, continued AR2480 AR2580 Height 2057 mm (81.0 in.) 2057 mm (81.0 in.) Width 800 mm (31.5 in.) 800 mm (31.5 in.) Depth 1060 mm (41.7 in.) 1200 mm (47.2 in.) Net weight 130.5 kg (287.7 lb) 139.5 kg (307.5 lb) Total open area front door 1 137 330 mm2 (1,763 in2) 1 137 330 mm2 (1,763 in2) Total open area rear door 1 171 657 mm2 (1,816 in2) 1 171 657 mm2 (1,816 in2) Open area per U front door 27 079 mm2 (42.0 in2) 27 079 mm2 (42.
48 U Cabinets AR2407 AR2507 Height 2324 mm (91.5 in.) 2324 mm (91.5 in.) Width 600 mm (23.6 in.) 600 mm (23.6 in.) Depth 1060 mm (41.7 in.) 1200 mm (47.2 in.) Net weight 123.5 kg (272.3 lb) 131.2 kg (289.2 lb) Total open area front door 900 609 mm2 (1,396 in2) 900 609 mm2 (1,396 in2) Total open area rear door 917 858 mm2 (1,423 in2) 917 858 mm2 (1,423 in2) Open area per U front door 187 63 mm2 (29.1 in2) 187 63 mm2 (29.1 in2) Open area per U rear door 19 122 mm2 (29.
48 U Cabinets, continued AR2487 AR2587 Height 2324 mm (91.5 in.) 2324 mm (91.5 in.) Width 800 mm (31.5 in.) 800 mm (31.5 in.) Depth 1060 mm (41.7 in.) 1200 mm (47.2 in.) Net weight 143.8 kg (317.0 lb) 152.8 kg (336.9 lb) Total open area front door 1 316 270 mm2 (2,040 in2) 1 316 270 mm2 (2,040 in2) Total open area rear door 1 334 498 mm2 (2,069 in2) 1 334 498 mm2 (2,069 in2) Open area per U front door 27 422 mm2 (42.5 in2) 27 422 mm2 (42.
Limited Factory Warranty The limited warranty provided by Schneider Electric in this Statement of Limited Factory Warranty applies only to Products you purchase for your commercial or industrial use in the ordinary course of your business. Terms of Warranty Schneider Electric warrants its products to be free from defects in materials and workmanship for a period of five years from the date of purchase.
IN NO EVENT SHALL SCHNEIDER ELECTRIC, ITS OFFICERS, DIRECTORS, AFFILIATES OR EMPLOYEES BE LIABLE FOR ANY FORM OF INDIRECT, SPECIAL, CONSEQUENTIAL OR PUNITIVE DAMAGES, ARISING OUT OF THE USE, SERVICE OR INSTALLATION, OF THE PRODUCTS, WHETHER SUCH DAMAGES ARISE IN CONTRACT OR TORT, IRRESPECTIVE OF FAULT, NEGLIGENCE OR STRICT LIABILITY OR WHETHER SCHNEIDER ELECTRIC HAS BEEN ADVISED IN ADVANCE OF THE POSSIBLY OF SUCH DAMAGES.
Worldwide Customer Support Customer support is available at no charge via e-mail or telephone. Contact information is available at www.apc.com/support/contact. ©2013 Schneider Electric, APC and the APC logo are owned by Schneider Electric Industries S.A.S., or its affiliated companies. All other trademarks are property of their respective owners.