Attach the server shelf to the mounted slides, install the cable management arm (optional), NetServer, and
bezel (optional).
9 To attach the server shelf to the
mounted slides, refer to Steps 2
and 3 in this table.
10 If you are installing the cable man-
agement arm:
Refer to the instructions supplied
with the HP NetServer Rack
Mount Kit to mount the cable man-
agement arm to the shelf.
To attach the cable management
arm to the NetShelter, place an M6
caged nut in the fourth mounting
hole above the bottom screw that
fastens the rail/slide assembly to
the vertical mounting rail. Use two
(2) M6 × 18mm screws and two
(2)M6cupwasherstomountthe
cable management arm to the rear
vertical rail.
Install and M6 × 12mm flat head
screw into the upper mounting
hole at the rear of the rail/slide
assembly, on the side opposite the
cable management arm.
11 Follow the procedures in the HP
NetServer Rack Mount Kit instruc-
tions to mount the server and bezel
(optional) to the shelf.
Note
: You will need to use M6 ×
18mm screws, M6 cup washers,
and M6 caged nuts in the top holes
of the bezel, in place of the HP-
supplied Timmerman nuts and dec-
orative screws.
Table 4: Installation Procedure for J1451A/B, J1452A/B, J1491A
Step Action Figure
M6 x 18mm
Screw
Cup
Washer
M6 x 12mm
Flat-head Screw
M6
Caged
Nut