Back-UPS BX650LI
User Guide
ON/OFF button
LED status indicator
A
D
C
B
Battery connector
AC power inlet
E
Battery and surge protected outlets
Fuse
Features
3
F
IEC jumper cablefor
PC connection
1
Safety and General Information
Inspect the package contents upon receipt. Notify the
carrier and dealer if there is any damage.
Readthe following reminders beforeinstalling the UPS.
• This UPS is intended for indoor use only.
• Connect the UPS power cable directly to a wall outlet. Do not use surge protectors or
extension cords.
• When grounding cannot be verified, disconnect the equipment from the AC power outlet
before installing or connecting to other equipment. Reconnect the power cord after all
connections are made.
• Servicing of batteries should be performed by Schneider Electric IT (SEIT) Customer
Support only.
• When replacing battery the UPS must be OFF, and its AC inlet unplugged.
• Do not dispose of batteries in a fire. The batteries may explode.
• Do not open or mutilate batteries. They contain an electrolyte that is toxic and harmful
to the skin and eyes.
• To avoid harmful injury due to energy hazard, remove wrist watches and jewelry such
as rings when replacing the batteries. Use tools with insulated handles.
• Replace batteries with the same number and type of batteries as originally installed in
the equipment.
2
Place and Power On
Replace PC's input cord with a jumper cable and use PC's input cord to connect
the UPS.
2
1
3
4
Connect the battery by pulling the battery handle up,
and then pushing it into the unit.
Press the ON/OFF button to turn on the unit.
The green “Power On” indictor confirms that the Back-UPS is on and ready to
provide protection.
The Back-UPS should charger for at least 6 hours to ensure sufficient runtime.
The unit is being charged whenever it is connected to AC power, whether the
unit is turned ON or OFF.
Place the Back-UPS to avoid:
Direct sunlight
Excessive heat
Excessive moisture
For safety operation, please place the unit on the floor.
4
Specifications
Input
Voltage / Frequency 230 VAC / 50 Hz or 60 Hz
Brownout Transfer /
Over-voltage Transfer
170 VAC, typical /
280 VAC, typical
Output UPS Capacity (total) 650 VA / 325 W
Voltage On Battery 230 Vac rms
Frequency - On Battery 50 Hz / 60 Hz ± 1Hz
TransferTime 6mstypical
Protection
AC Input Fuse
Battery
Type (maintenance-free) 12V, 7 AH
Typical Recharge Time 4-6 Hours
Physical
Net Weight 4.2 kg
Dimensions (H x W x D) 14.2 cm x 10.1 cm x 30 cm
Average Life
years. Environmental factors impact battery
life.Elevated temperatures, high humidity,
poor quality mains power, and frequent,
short duration discharges will shorten
battery life.
The battery typically lasts for three to five
The battery in the Back-UPS BX650LI
Series is not user-replaceable. Contact
SEITTechnical Support for a listof
authorized service centers near you.
APC by Schneider Electric IT Customer
Support Worldwide
For country specific customer support, go to the APC by Schneider Electric Web site, www.apc.com.
Troubleshooting and Service
1. If the problem persists, contact Schneider Electric IT (SEIT) Customer Support through the APC by
Schneider Electric Web site, www.apc.com.
.
a. Note the model number and serial number and the date of purchase. The model and serial numbers
are located on the rear panel of the unit and are available through the LCD display on select models.
b. Call SEIT Customer Support and a technician will attempt to solve the problem over the phone. If it
is not possible, the technician will issue a Returned Material Authorization Number (RMA#).
c. If the unit is under warranty,the repairs are free.
d. Service procedures and returns may vary internationally. Refer to the APC by Schneider Electric
Web site for country specific instructions.
2. Prepare to troubleshoot the problem over the phone. If this is not successful, and the unit is still under
warranty, the SEIT Technical Support Representative will provide all necessary information to return the
unit for replacement.
5
LED
Condition
On
Off On-line - The Back-UPS is supplying AC power to
the connected equipment
Constant Tone On Line Overload - The power being used by the
connected equipment has exceeded the capacity of the
unit. Disconnect some equipment.
Constant beeping Over-temperature Warning - The unit is
overheating and will shut down if the temperature is
not lowered. Disconnect some of the connected
equipment.
On
(Off during 4 beeps)
4 beeps repeated
every 30 seconds
On-Battery - The Back-UPS is supplying battery
power.
Flashing
Rapid Beeping
(every 1/2 second)
Low BatteryWarning - The Back-UPS has 2
minutes of runtime remaining.
Constant tone
Bad BatteryDetected - The battery needs to be
charged, or is at end of life. (See Battery
Replacement.)
Off
Shortbeepevery
4 seconds
Low Battery Shutdown - During On Battery
operation the battery power was almost completely
exhausted, and the Back-UPS is waiting for AC power
to return to normal.
Constant Tone On Battery Overload - The connected equipment
requires morepower thanprovided bythe Back-UPS
battery. Unplug devices one at a time to remove
overload. If the problem is not corrected, contact SEIT
Technical Support
Constant Tone Charger Fault - Back-UPS has an internal problem,
and is no longer powering the load. Contact SEIT
Technical Support
Audible Alarm
Long beep every
4 seconds
UPS has overheated and has shut down.
Unplug connected devices one at a time or
wait for a few hours for system to cool down.
Over-temperature Protected - The Back-
Status Indicators
Warranty
Register your product on-line. http://warranty.apc.com
The standard warranty is two (2) years from the date of purchase. SEIT standard procedure is to replace the
original unit with a factory reconditioned unit. Customers who must have the original unitback due to the
assignment of asset tags and set depreciation schedules must declare such a need at first contact with an SEIT
Technical Support representative. SEIT will ship the replacement unit once the defective unit has been
received by the repair department,or cross-ship upon the receipt of a valid credit card number. The customer
pays for shipping the unit to SEIT. SEITpays groundfreight transportation costs to ship the replacement unit
to the customer.
No-load Shutdown
If the UPS is operating on battery power and detects that the connected equipment is using less than
15W of energy for more than 15 minutes, it will shut down to conserve energy. When the UPS is
reconnected to AC power, the UPS will automatically switch on.
Operational Features
6
Automatic Voltage Regulation boosts/trims the AC voltage when it drops/exceeds safe levels.
This allows the equipment plugged into the unit to operate during low/high voltage conditions,
conserving the battery power in the event of a power cut.
The Back-UPS will switch to battery power if the input voltage level becomes too low/high for the
Automatic Voltage Regulation to compensate, or if the AC power is distorted.
Automatic Voltage Regulation (AVR)
Fuse Replacement
A spare fuse is provided in every Back-UPS unit.
Once the input current exceeds 5A, the installed
fuse in every unit will burn to safeguard connected
equipment from excessive input currents. Replace
it using the spare fuse, or with a fuse that has
similar input current rating.