Technical data

7InRow RD Technical Data Manual
Alarms
The microprocessor controller shall
activate a visible and audible alarm
in the following occurrences:
All series:
Cool Fail
Air filter clogged
Return air sensor fault
Supply air sensor fault
Rack temperature sensor fault
High discharge pressure
Low suction pressure
Fan fault
Water detected
Condensate pump fault
Air filter run hours violation
Group communication fault
Supply air high temperature
violation
Return air high temperature
violation
Filter DP sensor failure
Suction pressure sensor failure
Discharge pressure sensor failure
Persistent high discharge pressure
fault
Rack inlet temperature high
violation
External communication fault
Internal communication fault
On standby input contact fault
A-link isolation relay fault
Excessive compressor cycling
ACRD100 series and ACRD200
series only:
Condensate pan full
Upper fan power supply fault
Lower fan power supply fault
Suction temperature sensor failure
Persistent low suction pressure fault
ACRD200 series only:
Condenser fluid valve actuator fault
Outdoor heat exchanger (OHE) fault
Factory configuration not completed
Liquid refrigerant sensor failure
ACRD500 series only:
Compressor drive communication
fault
Compressor drive fault
Compressor drive warning
Compressor run hours violation
Condensate pump run hours
violation
Fan run hours violation
Supply humidity sensor fault
High suction pressure