Technical data

InRow RD Technical Data Manual24
General Data
General Specifications - ACRD200 Series
Data Units Water Cooled Glycol Mixture Cooled
Nominal flow rate entering to the unit l/s (gpm) 0.64 (10.0) 0.64 (10.0)
Design entering temperature °C (°F) 29.4 (85.0) 40.6 (105.0)
Maximum heat rejection kW (Btu/hr) 15.2 (52,000) 15.2 (52,000)
Maximum glycol percentage % 0 40
Entering temperature range for 0.64 l/s (10 gpm) flow
rate entering to the unit
°C (°F) 12.8 - 43.3
(55.0 - 110.0)
12.8 - 43.3
(55.0 - 110.0)
Unit pressure drop at 0.64 l/s (10 gpm) kPa (psi) 33.1 (4.8) 43.4 (6.3)
Fluid-cooled
MODEL ACRD200 Series
AIR SYSTEM - FAN (Standard Filter Installed)
Size - mm (in) 200 (7.9)
Air Volume - l/s (SCFM) 1080 (2290)
Fan Motor - W (HP) each 115 (0.15)
Number of Fans
6
COOLING COIL - COPPER TUBE/ALUMINUM FIN
Face Area - m
2
(ft
2
)
0.37 (3.97)
Rows Deep 2
FILTERS - WASHABLE (STANDARD)
Quantity 2
Size - mm (in) 238 X 933 (9.375 X 36.75)
Depth - mm (in) 13 (1/2)
Efficiency (%) <20% MERV 1
FILTERS - PLEATED (OPTIONAL)
Quantity 2
Size - mm (in) 238 X 933 (9.375 X 36.75)
Depth - mm (in) 51 (2)
Efficiency (%) 30% MERV 8
PHYSICAL DATA
Weight - kg (lbs) 199.09 (438)
Height - mm (in) 1991 (78.39)
Width - mm (in) 300 (11.8)
Depth - mm (in) 1070 (42.13)
CONNECTION SIZES
Liquid
In 7/8-in O DF brazed
Return 7/8-in ODF brazed
Condensate Drain
Drain Line - in 3/16-in ID, 5/16-in OD
REFRIGERANT
Type R410A
Charge - kg (oz) 2.2 (78)