Technical data

InRow RD Technical Data Manual38
Air Cooled Condensers - Electrical Data (ACRD100 Series)
SKU Voltage Phase Frequency FLA MCA MOP
ACCD75214 208-240V 1 ph 60 Hz 4.8 15 15
ACCD75215 208-240V 1 ph 60 Hz 4.8 15 15
ACCD75216 380-415V 3 ph 50 Hz 1.35 N/A N/A
ACCD75217 380-415V 3 ph 50 Hz 2.7 N/A N/A
ACCD75218 220-240V 1 ph 50 Hz 3.0 N/A N/A
ACCD75219 220-240V 1 ph 50 Hz 6.0 N/A N/A
ACCD75220* 220-240V 1 ph 50 Hz 3.0 N/A N/A
*ACCD75220 is CCC certified for use in China.
FLA=Full Load Amps
MCA=Minimum Circuit Amperes
MOP=Maximum Overcurrent Protection
Air Cooled Condensers - Electrical Data (ACRD500 Series)
SKU Voltage Phase Frequency FLA MCA MOP
ACCD75201 208-230V 3 ph 60 Hz
7.0 15.0 25
ACCD75202 208-230V 3 ph 60 Hz
14.0 20.0 35
ACCD75203 208-230V 3 ph 60 Hz
21.0 22.8 40
ACCD75204 460V 3 ph 60 Hz
3.5 15.0 15
ACCD75205 460V 3 ph 60 Hz 7.0 15.0 15
ACCD75206 460V 3 ph 60 Hz 10.5 15.0 20
ACCD75207 400V 3 ph 50 Hz 3.1 N/A N/A
ACCD75208 400V 3 ph 50 Hz 6.2 N/A N/A
ACCD75209 400V 3 ph 50 Hz 6.2 N/A N/A
FLA=Full Load Amps
MCA=Minimum Circuit Amperes
MOP=Maximum Overcurrent Protection
Fluid Coolers - Electrical Data (ACRD200 Series)
SKU Voltage Phase Frequency FLA MCA MOP
ACFC75210 460V 3 ph 60 Hz 2.6 15 15
ACFC75255 480V 3 ph 60 Hz 1.3 15 15
ACFC75256 380-415V 3 ph 50 Hz 2.7 N/A N/A
ACFC75257 380-415V 3 ph 50 Hz 2.7 N/A N/A
FLA=Full Load Amps
MCA=Minimum Circuit Amperes