User`s guide

InRow RD 100-Series and InRow RD 200-Series User’s Guide41
Administration: Notification and Logging
Event Actions
Path: Administration > Notification > Event Actions > options
Types of notification
You can configure event actions to occur in response to an event or group of events. These actions notify
users of the event in any of several ways:
Active, automatic notification. The specified users or monitoring devices are contacted directly.
E-mail notification
–SNMP traps
Syslog notification
Indirect notification in the event log. If no direct notification is configured, users must check the
log to determine which events have occurred.
For another method of indirect notification, see “SNMP” on page 37. SNMP enables an NMS
to perform informational queries. For SNMPv1, configuring the most restrictive SNMP
access type, READ, enables informational queries without the risk of allowing remote
configuration changes.
You can also log system performance data to use for device monitoring. See “Data log” on
page 21 for information on how to configure and use this data logging option.
Configuring event actions
Notification Parameters. For events that have an associated clearing event, you can also set the
following parameters as you configure events individually or by group, as described in the next two
sections. To access the parameters, click the receiver or recipient name.
Parameter Description
Delay x time before sending If the event persists for the specified time, notification is sent. If the condition
clears before the time expires, no notification is sent.
Repeat at an interval of x time The notification is sent at the specified interval (e.g., every 2 minutes).
Up to x times During an active event, the notification repeats for this number of times.
Until condition clears The notification is sent repeatedly until the condition clears or is resolved.