Operating instructions

21InRoom Controller - Operating Instructions
5. Controller start
After having switched on the power supply of the InRoom Controller the window
illustrated at the right will appear. This window displays the maximum number
of 32 bus participants (bus ID 0-31).
An I/O controller is displayed by a square frame containing the local tempe
-
rature and humidity. A gray frame signifies that the unit is in a stop state, and
a black frame indicates that the unit is in operation. An IOC symbol without
measured values indicates that the IOC is not reachable, either because it is
switched off (no voltage) or due to a bus fault. The other symbols contain an
abbreviation for the controller type:
AT - InRoom Controller,
ME - InRoom Controller at which these windows are displayed.
The bus-ID can be deducted from the location in the scheme. Line 1 contains
the bus participants 0 - 7 from left to right; line 2, 8-15; line 3, 16-23; line 4,
24-31.
A space signifies that a unit with a corresponding bus-ID does not exist.
A symbol/unit that is selected displays inversely. In the window on top of the
page the InRoom Controller is selected. It appears inversely with white letters
on a black background. In the window below, the IOC is selected.
The context status line contains the bus-ID and the global address of the
selected bus participant.
The global status line contains the bus-ID, the global address of the InRoom
Controller, and the clock.
Mark the last bus participant position 31 to access the screen illustrated to
the right. The entire system can be switched off in this state by using the local
on/off key.
All units are switched on and off by pressing the on/off key.
If you press the OK-button when all positions are marked the checkbus function
is carried out (after the request and entry of the service master password).
Use the selector key to navigate to the bus-ID of the InRoom Controller which
can be adjusted (after the request and entry of the service master password).
The global address cannot be adjusted here, for safety reasons.
The time can be adjusted by selecting the clock.
The following items can be adjusted in sequence:
context status line
global status line
- Year
- Month
- Day
- Hour
- Minute
- Second
bus-ID
global address