Operating instructions

81InRoom Controller - Operating Instructions
* 2
32
- 1 = 4294967295
6.4 Default configurations
Unit parameters Range Value
System name 20 characters System name
Unit name 20 characters Unit name
Unit ID 0 - 31 13
Global address 0 - 32767 1
Local stop 0 - 1 1
Monitoring stop 0 - 1 0
Sequencing stop 0 - 1 0
Terminal language
0:
English
1: German
1
PT language 1
Temperature unit 0: °C 1: °F 0
Temperature setpoint 5 - 35 24°C
Temperature setpoint, night 5 - 35 27°C
Humidity setpoint 5 - 90 45% r. h.
Winter start delay
0 - 300 180 s
Summer/winter change-over
5 - 35 16°C
Summer/winter hysteresis
1 - 9,9 2 K
Cooling priority 0: GE 1: CW 2: DX
0
Overload
0 - 9.9 0,0 K
Integral factor
0 - 10 0%
Output D common alarm 0 - 31 6
Output D winter operation 0 - 31 0
Input D remote on/off 0 - 43 0
Input D CW stop 0 - 43 0
Type
of control 1 - 4 1
Limiting control - start temperature 0 - 40 16°C
Limiting control - temp. gradient 0 - 20 0.5 K
Limiting control - humidity start 0 - 90 70% r.h.
Limiting control - humidity gradient 0 - 20 0,5%
Unit runtime
0 - 4294967295* 0 h
Stop time 0 - 4294967295 0 h
Cooling runtime
0 - 4294967295 0 h
Heating runtime
0 - 4294967295 0 h
Humidification runtime
0 - 4294967295 0 h
Dehumidification runtime
0 - 4294967295 0 h
Last service - day
1 - 31 1
Last service - month
1 - 12 8
Last service - year
0 - 255 4
Service interval
0 - 20 6
UPS - input D
0 - 43 0
UPS - cooling admitted
0 - 1 1
UPS - heating admitted
0 - 1 1
UPS - humidification admitted
0 - 1 1
UPS - dehumidification admitted
0 - 1 1