Operating instructions

InRoom Controller - Operating Instructions82
Alarms Range Fire Water Phase
Alarm input
D 0 - 43 0 0 0
Alarm priority
0 - 31 0 0 0
Common alarm
0 - 1 1 1 1
Alarm delay
0 - 100 5 s 5 s 5 s
Zone parameters Range Value
Zone 1 - 32 0
Sequencing time 0 - 65535 0 h
Test se
quencing 0 - 1 0
Valid alarm
s 1 - 26 all valid
Number of defective units
0 - 32 0
Emergency temperature
0 - 40 16°C
Zone fan speed
nMax 60 - 100 85%
CW standby
management 0 - 1 0
Room temperature Supply temperature Water temperature
min max min max min max
Value
5°C (0-20) 35°C (15-40) 5°C (0-20) 35°C (15-40) -20°C (-20-30) 45°C (10-50)
Alarm delay
30 s (0-300) 30 s (0-300) 30 s (0-300) 30 s (0-300) 30 s (0-300) 30 s (0-300)
Alarm priority
0 (0-31) 0 (0-31) 0 (0-31) 0 (0-31) 0 (0-31) 0 (0-31)
Common alarm
1 1 1 1 1 1
Room humidity Supply humidity
min max min max
Value
5%h.r (0-50) 90%h.r (50-100) 5%h.r (0-50) 90%h.r (50-100)
Alarm delay
30 s (0-300) 30 s (0-300) 30 s (0-300) 30 s (0-300)
Alarm priority
0 (0-31) 0 (0-31) 0 (0-31) 0 (0-31)
Common alarm
1 1 1 1
Data logger 1 Data logger 2
Data number
0 (0 - 1440) 0 (0 - 1440)
Interval
0 min (0 - 60000) 0 min (0 - 60000)
Type
1 (1 - 15) 1 (1 - 15)
General alarms
Limit alarms
Data logger
The parameter "zone" is not a zone pa-
rameter but can be adjusted separately
for each unit.
Due to its context it is displayed in this
table.
Hour Range 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23
monday
0 - 2 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1
tuesday
0 - 2 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1
... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ...
sunday
0 - 2 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1
Week program
The values in brackets dis-
play the range.