Operating instructions

InRoom Controller - Operating Instructions86
Range Dehumidifier
Start
0 - 100 10 %r.h.
Stop hysteresi
s 0 - 30 5 %r.h.
Dehumidification stop
0 - 10 5 K
Dehumidif. valve conf. 0 - 1 0
Bypass valve conf.
0 - 1 0
Output D 0 - 31 5
min water temp. 0 - 50 5°C
max water temp. 0 - 50 14°C
Range Fan 1 Fan 2 Fan 3
Type
1 - 2 2 2 2
Speed nMax 40 - 100 85% 85% 85%
Speed CW nMax 40 - 100 85% 85% 85%
Offset -10 - 10 0% 0% 0%
Pre-start
0 - 100 10 s 10 s 10 s
Overrun
0 - 100 60 s 60 s 60 s
Start temperature
0 - 9.9 0 K 0 K 0 K
Start speed
0 - 10 0 % 0 % 0 %
100% start time 0 - 100 5 s 5 s 5 s
Reduction time 30 - 120 30 min 30 min 30 min
Reduction speed 0 - 100 0 % 0 % 0 %
Dehumidific. r
eduction 0 - 20 0 % 0 % 0 %
UPS reduction 0 - 20 0 % 0 % 0 %
Filter offset 0 - 10 0 % 0 % 0 %
Minimum speed
0 - 100 70 % 70 % 70 %
Output D 0 - 31 1 2 9
Output A 0 - 20 1 0 0
Alarm input
D 0 - 43 1 2 15
Alarm priority
0 - 31 0 0 0
Common alarm
0 - 1 1 1 1
Alarm delay
0 - 100 10 s 10 s 10 s
Filter alarm input
D 0 - 43 5 5 3
Filter alarm priority
0 - 31 0 0 0
Filter common alarm
0 - 1 1 1 1
Filter alarm delay
0 - 100 20 s 20 s 20 s
Emergency start
0 - 9.9 0 K 0 K 0 K
Emergency speed 0 - 100 0 % 0 % 0 %
Control cycle 0 - 10 5 s 0 s 0 s
Max. alternation
0 - 10 2 % 0 % 0 %
Control factor
0 - 10 4 0 0
Component configure
d 0 - 1 1 0 0
Runtime
0 - 4294967295 0 h 0 h 0 h
Dehumidifier
Fans