Technical Specifications InRow™ Direct Expansion Air Conditioners Air-Cooled/Fluid-Cooled Up to 37 kW
American Power Conversion Legal Disclaimer The information presented in this manual is not warranted by the American Power Conversion Corporation to be authoritative, error free, or complete. This publication is not meant to be a substitute for a detailed operational and site specific development plan.
Table of Contents Technical Data............................................................................................ 1 Model Identification . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1 Model identification label location . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 Model Descriptions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Microprocessor Controller . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .10 Microprocessor controller . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Open Architecture . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Control Type . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Functions . . . . . . . . . . .
series) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42 Air-cooled piping access–top view, looking down (ACRD500/ACRP100 series) . . 43 Air-cooled piping access – bottom view, looking up (ACRD500/ACRP100 series) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44 Outdoor Heat Exchangers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Technical Data Model Identification Model identification label location 300 mm 600 mm Nameplate Rear Nameplate Model Descriptions Humidifier/ Reheat Power Air-cooled No 208–230 1-Phase 60 Hz Up to 10 kW Air-cooled No 220–240 1-Phase 50 Hz 300 mm Up to 10 kW Fluid-cooled No 208–230 1-Phase 60 Hz ACRD201 300 mm Up to 10 kW Fluid-cooled No 220–240 1-Phase 50 Hz ACRD500 600 mm Up to 37 kW Air-cooled No 200–240 3-Phase 50/60 Hz ACRD501 600 mm Up to 37 kW Air-cooled No 460–480 3
Standard Features and Options The modular, row-based computer room cooling system offers efficient, predictable, and economical cooling for a variety of spaces. Critical environmental requirements now reach far beyond the confines of the traditional data center or computer room to encompass a larger suite of applications, referred to as technology rooms.
Standard Features All series: • Variable-speed fans • Remote shutdown input • Common alarm output • Internal condensate pump • Top or bottom piping • Network Management Card (NMC) • Remote temperature sensors • Microprocessor controller • Insulated cabinet ACRD100 series and ACRD200 series only: • Washable filter • Condensate management with two dual floats • Condensate pumps • Scroll compressor • Hot gas bypass • 2-way/3-way floating point valve (ACRD200 series only) • Liquid line solenoid valve (ACRD100
Accessories • Cable leak detector • Baying kit-InRow DX to NetShelter VX rack • NetShelter SX 42-U to 48-U height adapters • NetShelter VX 42-U height adapters • Bridge trough power cable shield • Data cable bridge partition • Isolation ball valves (ACRD100 series only) • Fluid cooler • Condenser • Aisle containment • Rack containment 4 InRow™ Direct Expansion Air Conditioners Technical Specifications 990-4617
Scalable Solution for Critical Environments InRow Advantages The row-based solution improves energy efficiency and cooling ability in a number of ways. First, the InRow DX draws air directly from the hot aisle, allowing the InRow DX to take advantage of higher heat transfer efficiency due to higher temperature differences. It can then discharge room-temperature air directly in front of the servers it is cooling.
Cabinet The frame is constructed of 16 gauge formed steel for maximum strength. The cabinet is serviceable from the front and rear. All exterior panels and corner posts on the frame are powder coated for durability and an attractive finish. The front and rear exterior panels are constructed of 18 gauge perforated steel with 69.5% open free area. All panels, which include a key latch for safety and security, allow easy access and removal. Insulation (ACRD100 and ACRD200 series only) is 80.
Condensate pump ACRD100 and ACRD200 series: A condensate pump is factory wired and piped internally to the condensate drain pan. The pump is capable of pumping 34 l/h (9 g/hr) against head pressures of up to 50 ft (15.2 m) of total run. Of that run, 16 ft (4.9 m) can be vertical lift as measured from floor level. Dual floats are included with the unit. One float is used for condensate pump control, and the other float generates a condensate pump failure alarm.
Optional Features Cable water detector A leak detection cable is placed on the floor or subfloor around all possible leak sources. If water or other conductive liquids contact the cable anywhere along its length, the microprocessor controller announces the leak visually, audibly, and across the network. The 6.1-m (20-ft) cable may be cascaded to make custom lengths up to 24.4 m (80-ft). Network cable Various lengths of network cable are available to ship with your cooling system.
Hot Aisle Containment System Modular ceiling tiles and doors can be used to enclose the hot aisle. This increases the densities that can be handled in a single rack enclosure by eliminating mixing of hot and cold air streams. This method, called load neutralization, removes the heat from the hot aisle, cools it, and then returns it to the surrounding room area at or slightly below room temperature.
Microprocessor Controller Critical Alarm LED Warning Alarm LED Check Log LED Status LED Liquid Crystal Display (LCD) Menu Selection scroll keys Escape key Enter key Help key Microprocessor controller The microprocessor controller is standard on each system.
Control The backlit, four-line by twenty-character display is password configurable.
ACRD200 series only: • Condenser fluid valve actuator fault • Outdoor heat exchanger (OHE) fault ACRD500/ACRP100 series only: • Compressor drive communication fault • Compressor drive fault • Compressor drive warning • Compressor run hours violation • Condensate pump run hours violation • Fan run hours violation • Invalid supply setpoint • Idle mode active • High pressure switch active • Compressor high pressure • Supply humidity sensor fault • High suction pressure • Excessive compressor cycling ACRP100 se
InRow DX Models Exterior components: ACRD100 and ACRD200 series 990-4617 Removable rear door Adjustable leveling feet Side panel latch Display interface Removable side panel Removable front door Rear casters (non-swiveling) Door lock (front and rear) Front casters (swiveling) InRow™ Direct Expansion Air Conditioners Technical Specifications 13
Interior components (front): ACRD100 series 14 Electrical control box 1 (retractable) Compressor Electrical control box 2 Front air block panel Return air temperature sensor Evaporator fans (6 total) Condensate pan floats (2 total) Expansion valve Condensate pan Evaporator coil InRow™ Direct Expansion Air Conditioners Technical Specifications 990-4617
Interior components (rear): ACRD100 series Filter/dryer Hot gas bypass valve Pressure transducer (2 total, located behind air block) Liquid line shutoff solenoid Filter differential pressure port Electrical control box 1 Air filter (2 total) Power supply unit (bottom) Condensate pump (2 total) Power supply unit (top) Electrical control box 2 Sight glass 990-4617 Service junction box (top entry shown) InRow™ Direct Expansion Air Conditioners Technical Specif
Interior components (front): ACRD200 series 16 Electrical control box 1 (retractable) Compressor Electrical control box 2 Front air block panel Condensate pumps Evaporator fans (6 total) Bypass shutoff valve (2-way) Condensate pan Water control actuator Condensate pan floats (2 total) Water regulating valve (3-way) Brazed plate heat exchanger Expansion valve ! Evaporator coil InRow™ Direct Expansion Air Conditioners Technical Specifications 990-4617
Interior components (rear): ACRD200 series Filter/dryer Electrical control box 2 Pressure transducer (2 total, located behind airblock) Hot gas bypass valve Suction line Power supply unit (bottom) Filter differential pressure port Power supply unit (top) Air filters (2 total) Service junction box (top entry shown) Sight glass 990-4617 InRow™ Direct Expansion Air Conditioners Technical Specifications 17
Exterior components: ACRD500/ACRP100 series 18 Removable rear doors Casters (all swiveling) Side panel lock Door handle and lock Removable side panel Display interface Adjustable leveling feet Removable front door InRow™ Direct Expansion Air Conditioners Technical Specifications 990-4617
Interior components (front): ACRD500/ACRP100 series Electric heater (ACRP100 series only) Fan Condensate drain pan Fan guard Thermal expansion valve Electric Panel Compressor Customer Communications Interface Variable Frequency Drive (for compressor) Ladder diagrams Supply air temperature sensor Main circuit breaker 990-4617 Ground Wire ! Humidity sensor InRow™ Direct Expansion Air Conditioners Technical Specifications 19
na2074a Air-cooled interior components—ACRD500/ACRP100 series (back of unit) 20 Evaporator coil Shutoff valves (top piping only) Condensate drain pan Air filters Sight glass Pipe chase Filter dryer Humidity sensor (ACRP100 series only) Condensate pump Return air temperature sensor Humidifier (ACRP100 series only) InRow™ Direct Expansion Air Conditioners Technical Specifications 990-4617
Electrical panel: ACRD100 and ACRD200 series Leak detector port Building management system (BMS) RS-485 port Remote temperature sensor port Control RS-485 port A-Link ports Form C and shutdown input Reset button RS-232 console port Network port Outdoor heat exchanger (OHE) input and output ports (optional connection for ACRD100 and ACRD101) 990-4617 InRow™ Direct Expansion Air Conditioners Technical Specifications 21
Electrical panel:ACRD500/ACRP100 series Transformers User interface connectors Main controller board Relay board Ground lug Main circuit breaker • Compressor fuse block (ACRP100, ACRP101, ACRD500, ACRD501 OR • Compressor circuit breaker (ACRP102 and ACRD502) Fan circuit breakers Controller circuit breaker Humidifier circuit breaker (ACRP100 series) Heater circuit breaker (ACRP100) Heater contactors (ACRP100 series) Humidifier contactor (ACRP100) Note: For a to
User interface panel: ACRD500/ACRP100 series Rack inlet temperature sensors 1, 2, 3 A-Link IN A-Link OUT Network port Console port Alarm output, NC (Normally Closed) Alarm output, COM (Common) Alarm output, NO (Normally Open) Supply GND (Ground) Supply 12 VDC (current limit: 20 mA) Supply 24 VDC (current limit: 20 mA) Remote shutdown+ (12–30 VAC/VDC, 24 VDC @ 11 mA) Remote shutdown- 990-4617 ! BMS D1 (RXTX+) " BMS D0 (RXTX–) # BMS GND $ Supply air tem
Performance Specifications Net cooling capacity (air and glycol cooled) Return Air Temperature Model 22.2°C DB, 15.5°C WB (72°F DB, 60°F WB) 23.9°C DB, 16.2°C WB (75°F DB, 61.1°F WB) 26.7°C DB, 19.4°C WB (80°F DB, 67.0°F WB) 26.7°C DB, 17.1°C WB (80°F DB, 62.8°F WB) Total Capacity kW (BTU/hr) Sensible Capacity kW (BTU/hr) ACRD100 8.22 (28,000) 8.04 (27,400) ACRD101 8.01 (27,200) 7.71 (26,400) ACRD200 8.22 (28,000) 8.04 (27,400) ACRD201 8.01 (27,200) 7.
Return Air Temperature Model 43.3°C DB, 22.2°C WB) (110°F DB, 72.0°F WB 5 Airflow is reduced to 448 l/s (950 SCFM) at this condition to maintain adequate evaporating temperature. Total Capacity kW (BTU/hr) Sensible Capacity kW (BTU/hr) 5 10.6 (36,000) 10.6 (36,000) ACRD1015 10.5 (35,900) 10.5 (35,900) ACRD2005 10.6 (36,000) 10.6 (36,000) ACRD2015 10.5 (35,900) 10.5 (35,900) ACRD100 *Airflow reduced to 4000 SCFM at this condition to maintain adequate return gas temperature.
Performance at Percentage of Fan Speed ACRD100 series % Fan Speed Voltage/Phase/Hz L/S (SCFM) Unit Power in kW Condenser Fan Power Net Sensible Capacity kW SA Temp °C (°F) in kW (BTU/h) Return Air Temperature – 29.
% Fan Speed 90 100 990-4617 Voltage/Phase/Hz L/S (SCFM) Unit Power in kW 200-240/1/60 200-240/1/50 200-240/1/60 200-240/1/50 N/A N/A Condenser Fan Power Net Sensible Capacity kW SA Temp °C (°F) in kW (BTU/h) N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A InRow™ Direct Expansion Air Conditioners Technical Specifications 27
ACRD200 series % Fan Speed Voltage/Phase/Hz L/S (SCFM) Unit Power in kW Net Sensible Capacity kW (BTU/h) SA Temp °C (°F) 2.35 4.60 (15,710) 20.8 (69.5) 2.25 4.60 (15,710) 20.8 (69.5) 2.41 5.76 (19,671) 20.8 (69.5) 2.31 5.76 (19,671) 20.8 (69.5) 2.47 6.63 (22,643) 20.8 (69.5) 2.37 6.63 (22,643) 20.8 (69.5) 2.55 7.36 (25,136) 20.8 (69.5) 2.45 7.36 (25,136) 20.8 (69.5) 2.60 8.00 (27,321) 20.8 (69.5) 2.50 8.00 (27,321) 20.8 (69.5) 2.68 8.70 (29,712) 20.8 (69.5) 2.58 8.
% Fan Speed 100 Voltage/Phase/Hz Unit Power in kW L/S (SCFM) 200-240/1/60 N/A 200-240/1/50 Net Sensible Capacity kW (BTU/h) SA Temp °C (°F) N/A N/A N/A N/A N/A N/A ACRD500/ACRP100 series (No humidifier/no reheat) % Fan Speed Voltage L/S (SCFM) Unit Power in kW Condenser Fan Power in kW Net Sensible Capacity kW (BTU/h) SA Temp °C (°F) Return Air Temperature – 29.4°C (85°F) 30 All 700 (1400) 2.03 0.01 7.3 (24,931) 20.8 (69.5)* 40 All 900 (1800) 3.25 0.02 9.8 (33.469) 20.
General Data General Specifications – ACRD200 series Data Units Water Cooled Glycol Mixture Cooled Nominal flow rate entering to the unit l/s (GPM) 0.64 (10.0) 0.64 (10.0) Design entering temperature °C (°F) 29.4 (85.0) 40.6 (105.0) Maximum heat rejection kW (BTU/hr) 15.2 (52,000) 15.2 (52,000) Maximum glycol percentage % 0 40 Entering temperature range for 0.64 l/s (10 GPM) flow rate entering to the unit °C (°F) 12.8 - 43.3 (55.0 - 110.0) 12.8 - 43.3 (55.0 - 110.
Air-Cooled unit performance Data Model Value AIR SYSTEM - FAN (Standard Filter Installed) Size - mm (in) Air Volume - l/s (SCFM) Fan Motor - W (HP) each Number of Fans ACRD100 series 200 (7.9) ACRD500/ACRP100 series 400 (15.8) ACRD100 series 1080 (2290) ACRD500/ACRP100 series 2200 (4600) ACRD100 series 115 (0.15) ACRD500/ACRP100 series 1100 (1.5) ACRD100 series 6 ACRD500/ACRP100 series 2 COOLING COIL - COPPER TUBE/ALUMINUM FIN Face Area - m2 (ft2) Rows Deep ACRD100 series 0.37 (3.
Data Model Value ACRD100 series 183 (404) PHYSICAL DATA Weight - kg (lbs) Height - mm (in) Width - mm (in) Depth - mm (in) ACRD500 series 367 (808) ACRP100 series 372 (820) ACRD100 series 1991 (78.39) ACRD500/ACRP100 series 1991 (78.39) ACRD100 series 300 (11.8) ACRD500/ACRP100 series 600 (23.62) ACRD100 series 1070 (42.13) ACRD500/ACRP100 series 1070 (42.
Sound performance data ACRD100 and ACRD200 Series Tested Sound Data Fan Fan Speed % RPM Airflow m3/s (SCFM) Lp Sound Pressure dB re: 20 µPa* Sound Power dB at Frequency Hz re: 10-12W 125 250 500 1000 2000 4000 8000 dBA** dBA 60 2300 0.66 (1400) 62.3 68.3 69.8 74.8 67.8 59.3 53.3 76.5 70.5 70 3000 0.78 (1650) 65.3 76.3 74.8 77.8 73.8 67.8 61.3 80.8 74.7 80 3450 0.85 (1800) 67.3 80.3 77.3 78.2 76.3 71.8 66.3 82.7 76.6 90 3800 0.92 (1950) 68.3 81.8 78.
Electrical Data Model MCA** ACRD100 – 208-240V, 1 Ph, 60Hz ACRD101 – 220-240V, 1 Ph, 50Hz ACRD200 - 208-240V, 1 Ph, 60Hz ACRD201 – 220-240V, 1 Ph, 50Hz ACRD500 – 200-240V, 3 Ph, 50/60Hz ACRD501 – 460-480V, 3 Ph, 60Hz ACRD502 – 380-415V, 3 Ph, 50Hz ACRP100 – 200-240V, 3 Ph, 50/60Hz ACRP101 – 460-480V, 3 Ph, 60 Hz ACRP102– 380-415V, 3 Ph, 50/60Hz 25 N/A 25 N/A 54.0 27.0 N/A 80.1 39.9 N/A MOP** FLA** 40 N/A 40 N/A 90 40 N/A 100 50 N/A N/A 21 N/A 21 N/A N/A 26.0 N/A N/A 32 Compressor LRA 87.5 97.0 87.
Dimensional Data ACRD100/ACRD200 series Dimensions are shown in mm (in).
ACRD500/ACRP100 series Dimensions are shown in mm (in).
NetShelter SX to VX Height Adapter: ACRD100/ACRD200 series NetShelter SX to VX Height Adapter: ACRD500/ACRP100 series NetShelter SX to 48-U SX Height Adapter: ACRD100/ACRD200 series NetShelter SX to 48-U SX Height Adapter: ACRD500/ACRP100 series Dimensions are shown in mm (in).
Piping and Mechanical Connections Refrigeration piping diagram (ACRD100/ACRD500/ACRP100 series)) Bottom piping Top piping Condenser Liquid Liquid Hot gas Hot gas Condenser RD/RP Receiver Receiver RD/RP Note: Shutoff valves shown nearest to the condensers are not supplied by APC by Schneider Electric. ACRD500/ACRP100 series: The shutoff valves nearest to the cooling unit are supplied by APC by Schneider Electric. ACRD100 series: The shutoff valves are not supplied and must be ordered.
Water-cooled piping–bottom piping (ACRD200 series) InRow DX Gate valve* Balancing valve* Hose bib* Strainer, 20 mesh* *Field supplied and installed 990-4617 InRow™ Direct Expansion Air Conditioners Technical Specifications 39
Glycol-cooled bottom piping (ACRD200 series) Expansion tank* Gate valves* Tank fill* Balancing valve* Fluid-cooler Check valve Airtrol fitting* Pump package* Temperature and pressure gauges* Flow switch Air vent* Hose bibs* Strainer, 20 mesh* ! InRow RD *Field supplied and installed 40 InRow™ Direct Expansion Air Conditioners Technical Specifications 990-4617
Top piping and power access locations (ACRD100/ACRD200 series) Dimensions are shown in mm (in).
Bottom piping and power access locations–looking up (ACRD100/ACRD200 series) Dimensions are shown in mm (in).
Air-cooled piping access–top view, looking down (ACRD500/ACRP100 series) REAR—HOT AISLE FRONT—COLD AISLE Refrigerant discharge line Refrigerant liquid line Trough for communication cables Power connections Humidifier water supply (ACRP100 only) Condensate drain Note: Dimensions are shown in mm (in).
Air-cooled piping access – bottom view, looking up (ACRD500/ACRP100 series) REAR—HOT AISLE FRONT—COLD AISLE Humidifier water supply (ACRP100 series) Condensate drain Power connections Communication connections Condensate overflow Refrigerant discharge line Refrigerant liquid line Note: Dimensions are shown in mm (in).
Outdoor Heat Exchangers Air-cooled condensers – mechanical Data (ACRD100 series) Model Ambient Temp °C (°F) Sound Pressure * Air Quantity Fan Unit Connection Size Weight Capacity l/s (CFM) Qty. kW Hot Gas Liquid Kg (lbs) MBH/1F TD kW/1C TD ACCD75214 35 (95) / 40 (104) 65 2380 (5050) 1 1.1 1 1/8 in 7/8 in 82 (180) 2.43 ACCD75215 46 (115) 66 3040 (6450) 1 1.1 1 1/8 in 7/8 in 118 (260) 4.00 2.11 ACCD75216 35 (95) / 40 (104) 59 2140 (4530) 1 0.8 22 mm 18 mm 48 (105.
Air-cooled condensers – electrical data (ACRD100 series) Model Receiver FLA*** MCA*** MOP*** Qty Voltage Phase Frequency Receiver Model ACCD75214 208-240V, 1 ph, 60 Hz ACAC75009 1 4.8 15 15 ACCD75215 208-240V, 1 ph, 60 Hz ACAC75009 2 4.8 15 15 ACCD75216 380-415V, 3 ph, 50 Hz ACAC75009 1 1.35 N/A N/A ACCD75217 380-415V, 3 ph, 50 Hz ACAC75009 1 2.7 N/A N/A ACCD75218 220-240V, 1 ph, 50 Hz ACAC75009 1 3.0 N/A N/A ACCD75219 220-240V, 1 ph, 50 Hz ACAC75009 1 6.
ACCD75201 and ACCD75204 ACCD75202 and ACCD75205 ACCD75203 and ACCD75206 Dimensions are shown in mm (in). Note: Condensers shown above have eight 22 mm (0.875 in) mounting holes on their lower rails.
ACCD75207 ACCD75208 and ACCD75209 Condensers shown above have 16 mm (0.63 in) mounting holes on each of their lower legs.
ACCD75214 ACCD75215 ACCD75216, ACCD75218, and ACCD75220 ACCD75217 and ACCD75219 990-4617 InRow™ Direct Expansion Air Conditioners Technical Specifications 49
ACFC75210 ACFC75255 Dimensions are shown in mm (in).
ACFC75257 Dimensions are shown in mm (in).
Facility Planning Air-Cooled Model Input Voltage Fluid-Cooled ACRD100 ACRD101 ACRD500/ ACRP100 ACRD501 ACRP101 ACRD502 ACRP102 ACRD200 ACRD201 208–230 220–240 460–480 460–480 380–415 208–230 220–240 Phases 1 1 3 3 3 1 1 Frequency 60 50 50/60 60 50/60 60 50 Total NET Capacity – kW (BTU/hr) 9.9 (33800) 9.69 (33100) 29 (99000) 29 (99000) 29 (99000) 9.9 (33800) 9.69 (33100) 10.92 (37300)* 10.98 (37500)* Sensible NET Capacity – kW (BTU/hr) 9.9 (33800) 9.
Air-Cooled Model ACRD100 ACRD101 ACRD500/ ACRP100 Fluid-Cooled ACRD501 ACRP101 ACRD502 ACRP102 ACRD200 ACRD201 Piping Connections Top or Bottom Top or Bottom Top or Bottom Top or Bottom Top or Bottom Top or Bottom Top or Bottom Electrical Connections Top or Bottom Top or Bottom Top or Bottom Top or Bottom Top or Bottom Top or Bottom Top or Bottom Cable Type Water Detector Optional Optional Optional Optional Optional Optional Optional Capacity rated at the following conditions: Entering A
Warranty Three-Phase Power Products or Cooling Solutions One-Year Factory Warranty The limited warranty provided by American Power Conversion (APC™) in this Statement of Limited Factory Warranty applies only to products you purchase for your commercial or industrial use in the ordinary course of your business.
THERE ARE NO WARRANTIES, EXPRESS OR IMPLIED, BY OPERATION OF LAW OR OTHERWISE, OF PRODUCTS SOLD, SERVICED OR FURNISHED UNDER THIS AGREEMENT OR IN CONNECTION HEREWITH. APC DISCLAIMS ALL IMPLIED WARRANTIES OF MERCHANTABILITY, SATISFACTION AND FITNESS FOR A PARTICULAR PURPOSE. APC EXPRESS WARRANTIES WILL NOT BE ENLARGED, DIMINISHED, OR AFFECTED BY AND NO OBLIGATION OR LIABILITY WILL ARISE OUT OF, APC RENDERING OF TECHNICAL OR OTHER ADVICE OR SERVICE IN CONNECTION WITH THE PRODUCTS.
Guide Specifications Guide Specifications for InRow Direct Expansion THIS GUIDE SPECIFICATION IS WRITTEN IN ACCORDANCE WITH THE CONSTRUCTION SPECIFICATIONS INSTITUTE (CSI) MASTERFORMAT. THIS SECTION MUST BE CAREFULLY REVIEWED AND EDITED BY THE ARCHITECT OR THE ENGINEER TO MEET THE REQUIREMENTS OF THE PROJECT. COORDINATE THIS SECTION WITH OTHER SPECIFICATION SECTIONS IN THE PROJECT MANUAL AND WITH THE DRAWINGS. WHERE REFERENCE IS MADE THROUGHOUT THIS SECTION TO “PROVIDE”, “INSTALL”, “SUBMIT”, ETC.
1.4 A. QUALITY ASSURANCE The system shall be completely factory-tested prior to shipment. Testing shall include, but not be limited to: complete pressure and leak testing to ensure system integrity, “Hi-Pot” test, and controls calibration and settings. Each system shall ship with a completed test report to verify completion of factory testing procedure. The system shall be NTRL listed, MCA, and electrical system shall be UL Listed to UL 1995 and CSA 22.2 No. 236. PART 2 — PRODUCT 2.
C. MAIN DISCONNECT SWITCH (ACRD500/ACRP100 series) 1. Unit shall be provided with Thermal-Magnetic circuit breakers with interrupt capacity ratings per UL489/CSA C22.2/IEC-947. a. Voltage: 200–240V 50/60Hz /kAIC 50 b. Voltage: 380–415V 50Hz /kAIC 36 c. Voltage: 460–480V 60Hz /kAIC 22 2. Air-cooled: Units shall include a main disconnect switch located on the E-panel in order to disconnect power input (600 mm models only). 3. A condenser disconnect shall be field supplied. D. MICROPROCESSOR CONTROLLER 1.
b. ACRD100 series and ACRD200 series only: 1. Condensate pan full 2. Upper fan power supply fault 3. Lower fan power supply fault 4. Suction temperature sensor failure 5. Persistent low suction pressure fault 6. Factory configuration not completed 7. Liquid refrigerant sensor failure c. ACRD200 series only: 1. Condenser fluid valve actuator fault 2. Outdoor heat exchanger (OHE) fault d. ACRD500/ACRP100 series only: 1. Compressor drive communication fault 2. Compressor drive fault 3.
E. NETWORK MANAGEMENT CARD 1. The unit shall include a network management card to provide management through a computer network through TCP/IP. Management through the network should include the ability to change set points as well as view and clear alarms. F. COOLING COIL AND CONDENSATE PAN 1. ACRD100 and ACRD200 series Direct Expansion: The cooling coil shall use corrugated aluminum fin and copper tube coils.
J. FILTERS 1. ACRD100 series and ACRD200 series: a.The standard filters shall be 20% efficient per ASHRAE 52.1, MERV 1 per ASHRAE 52.2, 1/2 in washable mesh filter. b.The optional filter shall be high capacity 2 in pleated, UL 900 Class 2, moisture resistant, with average atmospheric dust spot efficiency of 30%, per AHRAE Standard 52.1, MERV 8 per ASHRAE 52.2. 2. ACRD500/ACRP100 a. The standard filters shall be 30% efficient per ASHRAE Standard 52.1, UL Class 2 (MERV 8 per ASHRAE 52.2).
4. Internal Humidity Sensors: Humidity sensors shall be mounted behind both the front and rear doors and shall provide control input based on humidity in supply air. Humidifier sensor shall be +/– 3% RH accuracy full scale. (ACRD500/ACRP100 series only) N. COOLING FLUIDS (ACRD200 Series) 1. Water and solutions of propylene or ethylene glycol up to 50% may be used. Solutions of brine or other aqueous salt are NOT permitted. O. FREEZE PROTECTION (ACRD200 Series) 1. Per ASHRAE Handbook Fundamentals 2001 21.
Worldwide Customer Support Customer support is available at no charge via e-mail or telephone. Contact information is available at www.apc.com/support/contact. © APC by Schneider Electric. APC and the APC logo are owned by Schneider Electric Industries S.A.S., American Power Conversion Corporation, or their affiliated companies. All other trademarks are property of their respective owners.